Q7 Integrated Enclosure Control Panel
Features
There are three types of Q7 Integrated Enclosure control panels available. The panel used will be a
function of the system features available for a given system. Two of the panels provide the user with control
and monitoring features and one is used as a cover for an unused panel mounting hole and has no active
features.
Figure 10
shows the three Q7 Integrated Enclosure panel types followed by a description of the applicable
features of each.
Figure 10. Available Q7 Panels.
Control Power LED (LED 5) — On when the control circuit power is available. This is not an
indication that power is off.
System Interlock LED (LED 4) — On when the following conditions are met:
•
Control Power is applied,
•
Door switch (LS) is closed,
•
Protective Overload contactor (OL) is closed,
•
Customer Interface contact (CI) is closed, and
•
The damper is fully open (DRA connected to DRB).
Inverter LED (LED 2) — On when the following conditions are met:
•
Control Power is applied,
•
Door switch (LS) is closed,
•
Protective Overload contactor (OL) is closed,
•
Customer Interface contact (CI) is closed, and
•
The Inverter Mode switch is switched to INV.
This closes the 1M and 2M contactors allowing for normal ASD operation.
Q7 ASD Installation and Operation Manual