Step 6 - Configure The Fire Panel; Step 7 - Test The System - Honeywell IPGSM-4G Installation And Setup Manual

Commercial fire communicator
Table of Contents

Advertisement

IPGSM-4G Commercial Fire Communicator – Installation and Setup Guide
To exit the programming mode, press [N] in response to the "Review?" prompt. Then press [Y] to the "Exit Prog
Mode?" prompt. Upon exiting, the root file is updated to log the changes made. A message is displayed telling the
user that this step is being executed. When complete, the message "DONE" is displayed to indicate the file was suc-
cessfully uploaded.
Note: If critical configuration changes were made, such as the mode of operation, the communicator
will reset to ensure that the programming features are enabled.
If the file is not successfully uploaded, one of the following prompts will be displayed. Follow the steps shown below
until the upload is successful.
Display
Cannot Upload
Try Again? Y/N_
Failed to Update
Root File!
Setting Factory Defaults
To reset the programming options to factory-default values, at the "Exit Prog Mode?" prompt press [Shift] plus [ESC].
Note, setting the factory defaults will also erase any password that may have been entered.
Press [Y] to reset factory default values.
Set Default?
Press [N] to cancel this function.
Y/N_
Press [Shift] then [Y], then [#]. The Create Password prompt appears, follow the prompts then exit.
STEP 6 – Configure the Fire Panel
1.
Ensure the Phone Line Supervision (or Telco Fault) on the panel is enabled. Then choose a setting that is no
higher than 90 seconds (or as close to that) as the panel allows.
2.
Ensure no more than 1 pause character (usually a comma) is programmed into the dialing string (usually 2 se-
conds). Note, this is necessary since the Dialer Capture Module waits only 3 seconds after the phone number
is dialed. Having more than 3 seconds of pause time will cause it to think the phone number is complete and
cause it to generate the high-low tones at an incorrect moment.
STEP 7 – Test the System
1.
Close the Wall Outlet Box, then close and lock the cabinet cover.
2.
Refer to the fire panel's installation/operation guide the testing procedure.
3.
(Notify the monitoring station that a test will be conducted.) Test the system to ensure it is operating.
4.
Verify communications with the monitoring station is successful by sending several events. Also, get confirma-
tion that these events were received.
Description
Communicator is not yet initialized.
Network problem, or you answered "N"
to "Cannot Upload Try Again?" prompt.
What to do
Wait for RSSI indicator LEDs to be lit.
Press [Y].
Initiate the Force Server Update
Command by pressing the [0] key.