PHASE ROTATION TEST
•
Perform a function test prior to this test.
•
This unit can determine the phase rotation
within a three-phase supply.
•
Connect the L2 test probe to the supported
phase 2 and the L1 test probe to the
supposed phase 1. If the R LED illuminates
the phases are in the correct sequence 1
to 2.
•
Connect the L2 test probe to the supposed
phase 3 and the L1 test probe to the
supposed phase 2.
•
If the R LED illuminates, the phases are in
the correct sequence 2 to 3.
•
Connect the L2 test probe to the supposed
phase 1 and the L1 test probe to the
supposed phase 3.
•
If the R LED illuminates the phases are in
the correct sequence 3 to 1.
•
During phase rotation, test touch the
contact electrode. If the LED illuminates
then the phase sequence is anti-clockwise.
SPECIFICATION
Voltage display
LED resolution
LCD resolution
Voltage detection
Acoustic signal
Polarity detection
Response time
Frequency range
Peak current
Operation time
Recovery time
Auto power-on
12 - 690V AC/DC
12, 24, 50, 120, 230, 400, 690
(12-690V AC/DC) ± 3% + 8 digits
Automatic
AC voltage - DC voltage
Full range
LED <0.1s, LCD <2s
0 - 400Hz
Is < 0.3A / is (after 5s) <3.5mA
30s
10 min
<12V AC/DC
6