Batch/Prime Mode

While in Run Mode (either of the ON or OFF LEDs are lit
and not blinking), press and hold the ON TIME
button (E) for five seconds to start batching. This will
turn the pump on for the duration of the programmed On
Time, which appears on the display (F) as it counts
down to "0". This can be used to prime the pump or to
force a pump to start a batch cycle immediately. (See
Keypad, Display, and Icons on page 4.)
Once the countdown is complete, the pump will return to
Run Mode and continue its cycle of Off and On accord-
ing to the setpoints entered in the On Time and Off Time
Setup Modes.
NOTE: The Batch/Prime Mode countdown can be can-
celed at any time by pressing any button. The pump will
return to Run Mode and normal operation.
3A8606A

Sleep Mode

While in Run Mode (either of the ON or OFF LEDs (A or
B) are lit and not blinking), press and hold the OFF TIME
button (C) for five seconds to put the controller in Sleep
Mode. To wake the controller, press and hold the OFF
TIME button (C) for five seconds. The controller will then
resume Run Mode and continue where it left off in its
cycle of Off and On Times.
Operation
9