Indications In Monitor Direction; Automatic Reclosure Status - Siemens SIPROTEC 7SJ61 Manual

Multifunction protection with control
Hide thumbs Also See for SIPROTEC 7SJ61:
Table of Contents

Advertisement

3.2

Indications in monitor direction

3.2.1
A
utomatic reclosure status
ASDU
Function
Informa-
type
tion
number
1
40
1
1
40
2
1
40
3
2
40
15
2
40
16
1
40
20
1
40
30
1
40
81
2
40
85
1
40
101
1
40
162
2
40
163
2
40
180
2
40
181
1
160
16
1
160
128
7SJ61 / 7SJ62 / 7SJ64 Bus mapping
C53000-L2540-A306-2
Name
>79 ON
>79 OFF
> BLOCK 79
>79 TRIP 1p
>79 TRIP 3p
>Enable ANSI#-2
>CB Ready
79 OFF
79 DynBlock
79 in progress
79 Successful
79 Lockout
79 L_N Sequence
79 L-L Sequence
79 ON
79 Close
Description
>79 ON; Automatic reclosure ON; ON = 1, OFF = 0
>79 OFF; ON = 1, OFF = 0
>BLOCK 79; ON = 1, OFF = 0
>Start 79 Ground programm; ON = 1, OFF = 0
>Start 79 Phase programm; ON = 1, OFF = 0
>Enable 50/67-(N)-2 (override 79 blk); ON = 1, OFF = 0
>Circuit breaker READY for reclosing; ON = 1, OFF = 0
79 Auto recloser is switched OFF; ON = 1, OFF = 0
79 – Auto-reclose is dynamically BLOCKED; ON = 1, OFF =
0
79 – in progress; ON = 1, OFF = 0
79 – cycle successful; ON = 1, OFF = 0
79 – Lockout; ON = 1, OFF = 0
79-A/R single phase reclosing sequence; Program earthfault
is running = 1, Program is deactivated = 0
79-A/R multi-phase reclosing sequence; ON = 1, OFF = 0
79 Auto recloser is switched ON; ON = 1, OFF = 0
79 – Close command; ON = 1
Point List
Obj. -
Adr.
2701
2702
2703
2715
2716
2720
2730
2781
2785
2801
2862
2863
2878
2879
2782
2851
27