Overview Overview PS9031-4820-0001 | Buffer module 48 V, 20 A, 100 ms • Buffering with electrolytic capacitors • Buffering of 48 V loads • Minimum hold-up time 0.1 s at 20 A, 0.2 s at 10 A and longer hold-up time with smaller loads • Clear status display by Status LED and signaling terminals •...
, XTS and XPlanar are registered trademarks of and licensed by Beckhoff Automation GmbH. Other designations used in this publication may be trademarks whose use by third parties for their own purposes could violate the rights of the owners. Patent Pending...
All the components are supplied in particular hardware and software configurations appropriate for the application. Modifications to hardware or software configurations other than those described in the documentation are not permitted, and nullify the liability of Beckhoff Automation GmbH & Co. KG. Personnel qualification This description is only intended for trained specialists in control, automation and drive engineering who are familiar with the applicable national standards.
Page 8
Foreword Safety information/installation requirements for PS9031-4820-0001 Buffer Module Danger of electric shock, fire, injuries, injuries resulting in death! • Switch off the power supply before working on the device. Provide protection against unintentional re- connection. • Do not modify or attempt to repair the device.
A value followed by the unit Vac or Vdc is an instantaneous value that does not contain any additional tolerances. A keyword indicating a choice without implied preference. shall A keyword indicating a mandatory requirement. should A keyword indicating a choice with a clearly preferred method of implementation. PS9031-4820-0001...
The buffer module requires no control wiring. It can be inserted anywhere in parallel with the load circuit. Buffer modules can be connected in parallel in order to increase the output current capacity or the hold-up time. 4: Parallel connection without control wiring PS9031-4820-0001...
Within the input voltage range the device can either be in power supply mode or buffer mode. Normal operating voltage range: The normal operating voltage range describes the supply voltage that supports the full functionality of the buffer module (including charging) without entering buffer mode. 7: Selection of a suitable power supply PS9031-4820-0001...
Page 13
Technical data, application notes, wiring 8: Output characteristic curve in buffer mode, 45 V fixed mode, typ. PS9031-4820-0001...
This setting is recommended for all applications in which 45 V is too low for the application or if the buffer module is placed near the power supply. The factory setting is fixed mode; if the jumper is missing, this also means fixed mode. PS9031-4820-0001...
Buffer time Min. 100 ms At 45 V, 20 A Min. 200 ms At 45 V, 10 A Typ. 150 ms At 45 V, 20 A Typ. 300 ms At 45 V, 10 A Typ. 21 s At 45 V, 0.1 A 9: Buffer time, typ. 10: Buffer time for low buffer currents, typ. PS9031-4820-0001...
Initial charging 17 s Recharging 25 s Recharging Initial charging is the first charging after applying the voltage to the buffer module. Recharging is the charging of the internal capacitors after voltage interruptions lasting less than 2 minutes. 11: Charging time, recharging PS9031-4820-0001...
9 is higher than 10 V. The buffering functions again below 6 V. Insulation voltage See chapter Dielectric strength [} 23] Efficiency and losses Efficiency Typ. >99% Power supply mode, 20 A output current, capacitors fully charged Power losses Typ. 1.9W Power supply mode, 0 A output current, capacitors fully charged PS9031-4820-0001...
10mm e* = solid wire f* = stranded wire a* = with ferrule 4.14 Connection diagrams 15: General connection diagrams; signals that are supplied by an external voltage source 16: Parallel connection of buffer modules; decoupling of buffered lines PS9031-4820-0001...
Technical data, application notes, wiring 4.15 Front side and operating elements 17: Front PS9031-4820-0001 Supply voltage terminals (quick-connect spring-loaded terminals) Designation (A) Description Positive supply voltage terminal (2x) Negative (back) supply voltage terminal (2x) Chassis ground terminal (quick-connect spring-loaded terminal)
According to IEC 60068-2-27 3 impacts/direction, 18 impacts in total The shock and vibration test takes place in combination with DIN rails according to EN 60715 with a height of 15 mm and a thickness of 1.3 mm and standard orientation. PS9031-4820-0001...
18: Dielectric strength Type test 500 Vac 500 Vac 500 Vac Component test 500 Vac 500 Vac 500 Vac Field test 500 Vac 500 Vac 500 Vac Settings for the field test cut-off > 1 mA > 1 mA > 1 mA current PS9031-4820-0001...
Applicable for US and Canada UK Declaration of Conformity: Trade conformity assessment for England, Scotland and Wales The UKCA mark indicates conformity with the UK Statutory Instruments 2016 No. 1101 (LVD) 2016 No. 1091 (EMC) and 2012 No. 3032 (RoHS) PS9031-4820-0001...
Housing material Housing: Aluminum alloy Cover: galvanized steel Ingress protection Small parts such as screws, nuts, etc. with a diameter greater than 3.5 mm Installation clearances See chapter on Safety instructions and installation requirements [} 8] 19: PS9031-4820-0001 – front/side view PS9031-4820-0001...
For lateral DIN rail mounting, the previously removed aluminum brackets and the black plastic slider must be mounted on the steel bracket. 21: Isometric view, wall mounting dimensioning, installation dimensions of the brackets for lateral mounting PS9031-4820-0001...
Please contact your Beckhoff branch office or representative for local support and service on Beckhoff products! The addresses of Beckhoff's branch offices and representatives round the world can be found on her internet pages: https://www.beckhoff.com You will also find further documentation for Beckhoff components there.