PHP A-1 Instruction Manual / Commissioning PHP A-1
STEP 7
Fill and ventilate the pressure maintenance pumps and
the piping.
• The shut off devices at the intake side of the pump(s) (1)
must be opened completely (ex factory)
• Remove the plug at the filler hole/use the de-aeration
possibility in the plug (2)
2
Figure: pump filling and ventilation
• If a EMCF-1 V makeup module is installed, go to manual
mode (user level 3), see chapter 5.7, "user level 3".
• Switch on the output "makeup valve Y1" ("output: on")
and fill the vessel until a continuous water jet leaks from
the filler hole at the pressure maintenance pump. After
this set the output "makeup valve Y1" to automatic mode
("output: auto"). The pump should be filled at a level
(reference value) of ca. 30 - 40%. During this filling the
vessel level can be watched at the main display.
• If a makeup module is not installed, you have do fill the
system until the vessel is filled via the overflow valve
and a continuous water jet leaks from the filler hole of
the pressure maintenance pump. If the system pressure
rises too high, you could reduce the set upper working
pressure at the overflow valve (see fig. 11).
• To ensure a complete ventilation, start and stop the
pump in manual mode ("output: Test", operate with "F1")
several times.
• Reassemble the plug of the pumps filler hole.
• AT devices with two pressure maintenance pumps
(systems PHP)‚ repeat the above steps for the second
pump (pump 1 = left side, pump 2 = right side)
• Open the emptying right beside the overflow valve and
ventilate the piping completely by starting and stopping
the pump(s) in manual mode several times. After this, shut
the emptying.
INFORMATION
Tip: Shut off all expansion vessels except the first main
vessel previously to accelerate the filling.
29
2
1
STEP 8
Configuration of the PHP device
• Press key "F2" (operate) in main display
• Select menu item "code input"
• Enter the code (see chapter 5.7. "user level 3")
• User level 3 is unlocked
• Go to menu item "device set-up" in user level 3 (if already
done: "settings" "device set-up")
User level 3
... device set-up
... vessel code
... acc. to the sticker at the vessel
... correction value PL1o
... acc. to the sticker at the upper
press. transmitter
... correction value PL1u
... acc. to the sticker at the lower
press. transmitter
... makeup EMCF-1 V
... not available (default setting)
... is available
... water treatment (only if makeup
EMCF-1 V is available)
... not available (default setting)
... softening MWE6 resp.
softening MWE12
... desalination MVE2 resp.
desalination MVE4
Degassing
... is available (default setting)
... not available
... bin. signalling (only if module
is installed)
... not available (default setting)
... is available
... remote acknowledgement
(only if module is installed)
... not available (default setting)
... is available
... analog signalling (only if module
is installed)
... not available (default setting)
... is available
... temperature sensor T2
... not available (default setting)
... is available
... level measurement L2
... not available (default setting)
... is available
... correction value PL2o