Electromagnetic Compatibility Guidelines - National Instruments cRIO-9034 Getting Started Manual

Embedded compactrio controller with real-time processor and reconfigurable fpga
Hide thumbs Also See for cRIO-9034:
Table of Contents

Advertisement

Caution
a minimum ingress protection rating of at least IP54 as defined in IEC/EN 60079-15.
Caution
tool.

Electromagnetic Compatibility Guidelines

This product was tested and complies with the regulatory requirements and limits for
electromagnetic compatibility (EMC) stated in the product specifications. These requirements
and limits provide reasonable protection against harmful interference when the product is
operated in the intended operational electromagnetic environment.
This product is intended for use in industrial locations. However, harmful interference may
occur in some installations, when the product is connected to a peripheral device or test object,
or if the product is used in residential or commercial areas. To minimize interference with
radio and television reception and prevent unacceptable performance degradation, install and
use this product in strict accordance with the instructions in the product documentation.
Furthermore, any changes or modifications to the product not expressly approved by National
Instruments could void your authority to operate it under your local regulatory rules.
Caution
shielded cables and accessories. The DC power input cables may be unshielded.
Caution
with the RS-485 serial port, such as NI part number 184428-01.
Caution
connected to the video, USB host ports, and V2 ports must be no longer than 3 m
(10 ft). The length of any cable connected to the RS-232 and RS-485 ports must be
no longer than 30 m (100 ft).
Caution
application deployment, debug, and maintenance.
Caution
either special considerations or user-installed, add-on devices. Refer to the following
sections for more information.
Related Information
Connecting the cRIO-9034 to Ground
Connecting the cRIO-9034 to Power
The system shall be mounted in an ATEX/IECEx-certified enclosure with
The enclosure must have a door or cover accessible only by the use of a
To ensure the specified EMC performance, operate this product only with
To ensure the specified EMC performance, you must use an isolated cable
To ensure the specified EMC performance, the length of any cable
The USB device port is intended only for use in device configuration,
To ensure the specified EMC performance, product installation requires
on page 7
on page 8
NI cRIO-9034 Getting Started Guide | © National Instruments | 3

Advertisement