See the table on the next page for more information regarding each terminal. 
F1 – fuse (maximum 0.5A) 
F1 
The fuse protects the electronic control board in case of short circuit from 
receiver or photo sensor 
F2 – fuse (maximum 15A) 
F2 
This fuse is part of the Safety design for the over current protection during 
the system operation. 
MM1 Terminal block 1 & 2 
Connect the cable to the MM1 for the master gate. 
J1 
(In gate opening operation, the master gate should be opened first) 
Important: connect only this interface if only using the single gate. 
SM2 Terminal block 3 & 4 
Connect the cable to the MM2 for the slave gate. 
J2 
(In gate closing operation, slave gate moves ahead of master gate with a 
few second of close delay) 
Terminal block  5 & 6 
J3 
Connect to the electric lock, 12VDC, Max current 3A 
Terminal block  7 & 8 
J3 
Connect to the flashing light. 12VDC, Max power 15W 
Terminal block  13+ve & 12 ‐ve 
J4 
Connect to the external receiver board for the 12 V DC ( Positive ) and Gnd 
( Negative ) 
Terminal block 10 
J4 
Connect to the push button or external receiver board for the dual gate 
operation 
Terminal block  11 
J4 
Connect to the push button or external receiver board for the single gate 
operation 
Terminal block 12 to 15 
 If using the photo sensor: connect the two (one is transmitter and other is 
receiver) photo sensors' +VDC to 13 and GND to 12. 
J4 
 Connect the N.C to 14 and COM to 15. 
 If NOT using the photo sensor, make a jumper between 14 and 15. 
Otherwise, the systems can't operate. 
Terminal block 16 
J5 
Connect Aerial cable 
Terminal block J6 
J6 
Connect to the Reset Switch 
SW2 
This button is used for code learning. 
VR1 
Over current limit can be adjusted from min 3.5Amp to Max 7.5Amp 
VR2 
Close delay can be adjusted from min 0 second to Max 8 second 