Pipe expanding method

Pipe expanding method
Note:
Improper pipe expanding is the main cause of refrigerant leakage. Please expand
the pipe according to the following steps:
A: Cut the pipe
●  Confirm  the  pipe  length  according  to  
the distance of indoor unit and
outdoor unit.
●  Cut  the  required  pipe  with  pipe  cutter.
pipe
leaning
B: Remove the burrs
●  Remove  the  burrs  with  shaper  and
prevent the burrs from getting into
the pipe.
downwards
C: Put on suitable insulating pipe
D:  Put  on  the  union  nut
●  Remove  the  union  nut  on  the  indoor
connection pipe and outdoor valve;
install the union nut on the pipe.
union pipe
pipe
pipe cutter
uneven
burr
pipe
shaper
E: Expand the port
●  Expand  the  port  with  expander.
Note:
●  "A"  is  different  according  to  the
diameter, please refer to the sheet
below:
Outer diameter
(mm)
Φ6-­6.35(1/4")
Φ9.52(3/8")
Φ12-­12.7(1/2")
Φ15.8-­16(5/8")
F: Inspection
●  Check  the  quality  of  expanding  port.  
If there is any blemish, expand the
port again according to the steps
above.
smooth surface
the length is equal
44
4
hard
mold
expander
A(mm)
Max
1.3
1.6
1.8
2.4
improper expanding
leaning
damaged
crack
surface
pipe
Min
0.7
1.0
1.0
2.2
uneven
thickness