Trilogy Q-Mode (QE) Series IOM - 60Hz HFC-410A ® ® R e v i s e d : D e c e m b e r 2 2 , 2 0 2 1 Model Nomenclature: General Overview 4 5 6 7 0 9 3 0 0 2 B L S STANDARD...
Trilogy Q-Mode (QE) Series IOM - 60Hz HFC-410A ® ® R e v i s e d : D e c e m b e r 2 2 , 2 0 2 1 General Information ⚠ ⚠ Inspection CAUTION! Upon receipt of the equipment, carefully check the shipment against the bill of lading.
Trilogy Q-Mode (QE) Series IOM - 60Hz HFC-410A ® ® R e v i s e d : D e c e m b e r 2 2 , 2 0 2 1 Vertical Installation Figure 1: Vertical Unit Mounting Using Ducted Return Sound Attenuation for Vertical Units Sound attenuation is achieved by enclosing the unit within a Internally insulate supply...
Page 6
Trilogy Q-Mode (QE) Series IOM - 60Hz HFC-410A ® ® R e v i s e d : D e c e m b e r 2 2 , 2 0 2 1 Vertical Installation (Cont.) Figure 3: Vertical Service Access Vertical Units Left Return Supply Air...
Page 7
Trilogy Q-Mode (QE) Series IOM - 60Hz HFC-410A ® ® R e v i s e d : D e c e m b e r 2 2 , 2 0 2 1 Horizontal Installation Horizontal Unit Location Mounting Horizontal Units Packaged units are not designed for outdoor installation.
Page 8
Trilogy Q-Mode (QE) Series IOM - 60Hz HFC-410A ® ® R e v i s e d : D e c e m b e r 2 2 , 2 0 2 1 Horizontal Installation (Cont.) Figure 5: Horizontal Service Access Left Return Back Discharge Right Return Back Discharge Supply...
HORIZONTAL INSTALLATION Figure 3: Typical Horizontal Unit Installation with Internal Flow Controller Trilogy Q-Mode (QE) Series IOM - 60Hz HFC-410A ® ® R e v i s e d : D e c e m b e r 2 2 , 2 0 2 1 Horizontal Installation (Cont.) 3/8"...
Page 10
Trilogy Q-Mode (QE) Series IOM - 60Hz HFC-410A ® ® R e v i s e d : D e c e m b e r 2 2 , 2 0 2 1 Horizontal Installation (Cont.) Field Conversion of Air Discharge Figure 7: Left Return Side to Back Overview - Horizontal units can be field converted Remove Screws...
Trilogy Q-Mode (QE) Series IOM - 60Hz HFC-410A ® ® R e v i s e d : D e c e m b e r 2 2 , 2 0 2 1 Condensate and Water Connection Condensate Piping Water Connections-Residential (Distributor) Models Pitch the unit toward the drain to improve the condensate Residential models utilize swivel piping fittings for water drainage.
Trilogy Q-Mode (QE) Series IOM - 60Hz HFC-410A ® ® R e v i s e d : D e c e m b e r 2 2 , 2 0 2 1 vFlow Heat Pump Applications Overview ® vFlow is a revolutionary new, intelligent, and efficient way to ®...
Trilogy Q-Mode (QE) Series IOM - 60Hz HFC-410A ® ® R e v i s e d : D e c e m b e r 2 2 , 2 0 2 1 Closed Loop Heat Pump Applications with Internal Flow Controller Units with internal flow control come with a built-in variable loop and it is also recommended for inside piping.
Page 14
Trilogy Q-Mode (QE) Series IOM - 60Hz HFC-410A ® ® R e v i s e d : D e c e m b e r 2 2 , 2 0 2 1 Closed Loop Heat Pump Applications with Internal Flow Controller Figure 13a: High Head Variable Pump with Check Valve UPMXL Internal Pump Flow (gpm)
Trilogy Q-Mode (QE) Series IOM - 60Hz HFC-410A ® ® R e v i s e d : D e c e m b e r 2 2 , 2 0 2 1 Flushing the Earth Loop ⚠ ⚠ Once piping is completed between the unit and the ground WARNING! loop, final purging and charging of the loop is needed.
Page 16
Trilogy Q-Mode (QE) Series IOM - 60Hz HFC-410A ® ® R e v i s e d : D e c e m b e r 2 2 , 2 0 2 1 Flushing the Earth Loop (Cont.) Figure 15b: Valve Position B - Unit Fill be sent through the loop to help purge air pockets from the piping system.
Page 17
Trilogy Q-Mode (QE) Series IOM - 60Hz HFC-410A ® ® R e v i s e d : D e c e m b e r 2 2 , 2 0 2 1 Flushing the Earth Loop (Cont.) pressurizing, close the flush cart supply valve to isolate the flush cart.
Trilogy Q-Mode (QE) Series IOM - 60Hz HFC-410A ® ® R e v i s e d : D e c e m b e r 2 2 , 2 0 2 1 Multiple Unit Piping and Flushing Often projects require more than one heat pump. Where For example, if a system includes two QE0930 units and four possible, it makes sense for multiple units to share a common ¾...
Page 19
Trilogy Q-Mode (QE) Series IOM - 60Hz HFC-410A ® ® R e v i s e d : D e c e m b e r 2 2 , 2 0 2 1 Multiple Unit Piping and Flushing (Cont.) Multiple Units with Internal Flow Controllers Multiple Units with Internal Flow Controllers and External The simplest multiple unit system is one with two (or more) Flushing Valves...
Page 20
Trilogy Q-Mode (QE) Series IOM - 60Hz HFC-410A ® ® R e v i s e d : D e c e m b e r 2 2 , 2 0 2 1 Multiple Unit Piping and Flushing (Cont.) Figure 16b: Multiple Units with Internal Flow Controllers and External Flushing Valves Multiple Units with Internal Flow Controllers and Common Flushing Ports Ground Loop Size for Heat Pump...
R e v i s e d : D e c e m b e r 2 2 , 2 0 2 1 Ground Loop Heat Pump Applications Antifreeze Selection - General Contact your ClimateMaster distributor if you have any In areas where minimum entering loop temperatures drop questions as to antifreeze selection.
Page 22
Trilogy Q-Mode (QE) Series IOM - 60Hz HFC-410A ® ® R e v i s e d : D e c e m b e r 2 2 , 2 0 2 1 Ground Loop Heat Pump Applications (Cont.) Low Water Temperature Cutout Setting - When anti-freeze is required, the tank should be drained immediately by is used in the ground loop heat exchanger, the unit configura- opening the waste valve of the flush cart noting the...
All closed water loop systems should undergo water quality testing and be maintained to the water quality standards listed in this table. CLIMATEMASTER WATER QUALITY STANDARDS For Closed-Loop and Open-Loop Systems Heat Exchanger Type...
Page 24
® R e v i s e d : D e c e m b e r 2 2 , 2 0 2 1 Water Quality Requirements (Cont.) 1. The ClimateMaster Water Quality Table provides Hydrogen Sulfide has an odor of rotten eggs. If α water quality requirements for coaxial & brazed one detects this smell, a test for H2S must be plate heat exchangers.
Page 25
Trilogy Q-Mode (QE) Series IOM - 60Hz HFC-410A ® ® R e v i s e d : D e c e m b e r 2 2 , 2 0 2 1 Water Quality Requirements (Cont.) Measuring Earth Ground Resistance �...
Trilogy Q-Mode (QE) Series IOM - 60Hz HFC-410A ® ® R e v i s e d : D e c e m b e r 2 2 , 2 0 2 1 Hot Water Mode The Trilogy unit provides significant savings when used to heat Configuring the Hot Water Mode domestic water.
Page 27
Trilogy Q-Mode (QE) Series IOM - 60Hz HFC-410A ® ® R e v i s e d : D e c e m b e r 2 2 , 2 0 2 1 Hot Water Mode (Cont.) Hot Water Figure 18: Typical Hot Water Piping Outlet Anti-Scald Valve Cold Inlet Shut Off #4...
Page 28
Trilogy Q-Mode (QE) Series IOM - 60Hz HFC-410A ® ® R e v i s e d : D e c e m b e r 2 2 , 2 0 2 1 Hot Water Mode (Cont.) The heat pump, water piping, and hot water tank should be Table 6: DHW Water Piping Sizes and Length located where the ambient temperature does not fall below ¾”...
Trilogy Q-Mode (QE) Series IOM - 60Hz HFC-410A ® ® R e v i s e d : D e c e m b e r 2 2 , 2 0 2 1 Electrical - Line Voltage ⚠ ⚠ WARNING! WARNING! To avoid possible injury or death due to electrical shock, open the power supply disconnect switch and secure it in an open position during installation.
Trilogy Q-Mode (QE) Series IOM - 60Hz HFC-410A ® ® R e v i s e d : D e c e m b e r 2 2 , 2 0 2 1 Electrical - Low Voltage Wiring Accessory Connections The EXM controller includes accessory relays.
Page 31
Trilogy Q-Mode (QE) Series IOM - 60Hz HFC-410A ® ® R e v i s e d : D e c e m b e r 2 2 , 2 0 2 1 Electrical - Low Voltage Wiring (Cont.) Figure 21a: Control Board for Units with Mitsubishi In- verter and Mitsubishi Interface Module (MIM) Low Voltage Field Wiring Figure 21b: Control Board for Units with Carel Inverter and...
Trilogy Q-Mode (QE) Series IOM - 60Hz HFC-410A ® ® R e v i s e d : D e c e m b e r 2 2 , 2 0 2 1 Electrical - Thermostat Wiring Thermostat Installation The Trilogy unit is designed to be utilized with the iGate Thermostat.
Trilogy Q-Mode (QE) Series IOM - 60Hz HFC-410A ® ® R e v i s e d : D e c e m b e r 2 2 , 2 0 2 1 EXM Wiring Diagram - 96B0005N64 This diagram includes typical wiring details but is not applicable to all units. For specific unit wiring, refer to the diagram or the units’ control panel. c l i m a t e m a s t e r .
Page 34
Trilogy Q-Mode (QE) Series IOM - 60Hz HFC-410A ® ® R e v i s e d : D e c e m b e r 2 2 , 2 0 2 1 EXM Wiring Diagram (Cont.) - 96B0262N01 G e o t h e r m a l H e a t i n g a n d C o o l i n g...
Trilogy Q-Mode (QE) Series IOM - 60Hz HFC-410A ® ® R e v i s e d : D e c e m b e r 2 2 , 2 0 2 1 ECM Blower Control ECM Blower Configuration Special Note for AHRI Testing: To achieve rated airflow for The ECM blower in the Trilogy unit is controlled by the EXM AHRI testing purposes, it is necessary to change the CFM microprocessor.
Trilogy Q-Mode (QE) Series IOM - 60Hz HFC-410A ® ® R e v i s e d : D e c e m b e r 2 2 , 2 0 2 1 ECM Blower Performance Data Trilogy Max ESP Cooling Heating Fan Only...
Trilogy Q-Mode (QE) Series IOM - 60Hz HFC-410A ® ® R e v i s e d : D e c e m b e r 2 2 , 2 0 2 1 System Configuration Configuring The iGate Connect Thermostat Capacity Configuration ™...
Page 38
Trilogy Q-Mode (QE) Series IOM - 60Hz HFC-410A ® ® R e v i s e d : D e c e m b e r 2 2 , 2 0 2 1 System Configuration (Cont.) Loop Configuration Configures the internal vFlow device to the application. The vFlow device will adjust the flow to maintain the selected temperature difference (Delta T) between the entering and leaving water for the active operating mode.
Page 39
Trilogy Q-Mode (QE) Series IOM - 60Hz HFC-410A ® ® R e v i s e d : D e c e m b e r 2 2 , 2 0 2 1 System Configuration (Cont.) Unit Manual Operation Compressor Diagnostics Manual Operation mode allows the service technician to Data Unit...
Page 40
Trilogy Q-Mode (QE) Series IOM - 60Hz HFC-410A ® ® R e v i s e d : D e c e m b e r 2 2 , 2 0 2 1 System Configuration (Cont.) Refrigerant Diagnostics Refrigerant Valve Diagnostics Data Unit Description...
Page 41
R e v i s e d : D e c e m b e r 2 2 , 2 0 2 1 System Configuration (Cont.) Dip Switch Settings An alternative method to configure (and diagnose) the Trilogy unit is ClimateMaster’s Trilogy PC Service Tool. This tool is a System Description Range/Options Default must for troubleshooting Trilogy units.
Page 42
Trilogy Q-Mode (QE) Series IOM - 60Hz HFC-410A ® ® R e v i s e d : D e c e m b e r 2 2 , 2 0 2 1 System Configuration (Cont.) Configuration: Service mode/ clear fault history The service tool software includes three pages of Enter service mode configuration data for your Trilogy and the following are...
Page 43
Trilogy Q-Mode (QE) Series IOM - 60Hz HFC-410A ® ® R e v i s e d : D e c e m b e r 2 2 , 2 0 2 1 System Configuration (Cont.) Sensor values Space Temp Space Humidity Upper Hot Water Tank Temp Lower Hot Water Tank Temp...
Trilogy Q-Mode (QE) Series IOM - 60Hz HFC-410A ® ® R e v i s e d : D e c e m b e r 2 2 , 2 0 2 1 Unit Commissioning and Operating Conditions Operating Limits Commissioning Conditions Environment –...
Trilogy Q-Mode (QE) Series IOM - 60Hz HFC-410A ® ® R e v i s e d : D e c e m b e r 2 2 , 2 0 2 1 Unit Start-Up and Operating Conditions ⚠ ⚠ Unit and System Checkout CAUTION! BEFORE POWERING SYSTEM, please check the following:...
Trilogy Q-Mode (QE) Series IOM - 60Hz HFC-410A ® ® R e v i s e d : D e c e m b e r 2 2 , 2 0 2 1 Unit Start-Up Procedure ⚠ ⚠ e. Check for warm air delivery at the supply air grilles WARNING! within a few minutes after the unit has begun to operate and that the loop water temperature drop is...
Trilogy Q-Mode (QE) Series IOM - 60Hz HFC-410A ® ® R e v i s e d : D e c e m b e r 2 2 , 2 0 2 1 Unit Operating Conditions Table 12a: 0930 Pressure and Temperature 0930 0930 Cooling...
Page 48
Trilogy Q-Mode (QE) Series IOM - 60Hz HFC-410A ® ® R e v i s e d : D e c e m b e r 2 2 , 2 0 2 1 Unit Operating Conditions (Cont.) Table 12b: 1860 Pressure and Temperature 1860 1860 Cooling...
Trilogy Q-Mode (QE) Series IOM - 60Hz HFC-410A ® ® R e v i s e d : D e c e m b e r 2 2 , 2 0 2 1 Performance Tables Legend CFM/T = airflow, cubic feet/minute per ton = Coefficient of Performance = BTU output/BTU input = entering water temperature, ˚F = leaving water temperature, °F...
Trilogy Q-Mode (QE) Series IOM - 60Hz HFC-410A ® ® R e v i s e d : D e c e m b e r 2 2 , 2 0 2 1 Table 13a: Performance Data — Trilogy QE 0930 - Heating ®...
Page 51
Trilogy Q-Mode (QE) Series IOM - 60Hz HFC-410A ® ® R e v i s e d : D e c e m b e r 2 2 , 2 0 2 1 Performance Data — Trilogy QE 0930 - Heating ®...
Trilogy Q-Mode (QE) Series IOM - 60Hz HFC-410A ® ® R e v i s e d : D e c e m b e r 2 2 , 2 0 2 1 Table 13b: Performance Data — Trilogy QE 0930 - Cooling ®...
Page 53
Trilogy Q-Mode (QE) Series IOM - 60Hz HFC-410A ® ® R e v i s e d : D e c e m b e r 2 2 , 2 0 2 1 Performance Data — Trilogy QE0930 - Cooling ®...
Trilogy Q-Mode (QE) Series IOM - 60Hz HFC-410A ® ® R e v i s e d : D e c e m b e r 2 2 , 2 0 2 1 Table 13c: Performance Data — Trilogy QE 0930 - Hot Water (Low) ®...
Trilogy Q-Mode (QE) Series IOM - 60Hz HFC-410A ® ® R e v i s e d : D e c e m b e r 2 2 , 2 0 2 1 Performance Data — Trilogy QE 0930 - Hot Water (High) ®...
Trilogy Q-Mode (QE) Series IOM - 60Hz HFC-410A ® ® R e v i s e d : D e c e m b e r 2 2 , 2 0 2 1 Table 13d: Performance Data — Trilogy QE 0930 - Cooling + Hot Water ®...
Page 57
Trilogy Q-Mode (QE) Series IOM - 60Hz HFC-410A ® ® R e v i s e d : D e c e m b e r 2 2 , 2 0 2 1 Performance Data — Trilogy QE0930 - Cooling + Hot Water ®...
Trilogy Q-Mode (QE) Series IOM - 60Hz HFC-410A ® ® R e v i s e d : D e c e m b e r 2 2 , 2 0 2 1 Table 14a: Performance Data — Trilogy QE 1860 - Heating ®...
Page 59
Trilogy Q-Mode (QE) Series IOM - 60Hz HFC-410A ® ® R e v i s e d : D e c e m b e r 2 2 , 2 0 2 1 Performance Data — Trilogy QE 1860- Heating ®...
Trilogy Q-Mode (QE) Series IOM - 60Hz HFC-410A ® ® R e v i s e d : D e c e m b e r 2 2 , 2 0 2 1 Table 14b: Performance Data — Trilogy QE 1860 - Cooling ®...
Page 61
Trilogy Q-Mode (QE) Series IOM - 60Hz HFC-410A ® ® R e v i s e d : D e c e m b e r 2 2 , 2 0 2 1 Performance Data — Trilogy QE 1860 - Cooling ®...
Trilogy Q-Mode (QE) Series IOM - 60Hz HFC-410A ® ® R e v i s e d : D e c e m b e r 2 2 , 2 0 2 1 Table 14c: Performance Data — Trilogy QE 1860 - Hot Water (Low) ®...
Trilogy Q-Mode (QE) Series IOM - 60Hz HFC-410A ® ® R e v i s e d : D e c e m b e r 2 2 , 2 0 2 1 Performance Data — Trilogy QE 1860 - Hot Water (High) ®...
Trilogy Q-Mode (QE) Series IOM - 60Hz HFC-410A ® ® R e v i s e d : D e c e m b e r 2 2 , 2 0 2 1 Table 14d: Performance Data – Trilogy QE 1860 - Cooling + Hot Water ®...
Page 65
Trilogy Q-Mode (QE) Series IOM - 60Hz HFC-410A ® ® R e v i s e d : D e c e m b e r 2 2 , 2 0 2 1 Performance Data — Trilogy QE 1860 - Cooling + Hot Water ®...
Trilogy Q-Mode (QE) Series IOM - 60Hz HFC-410A ® ® R e v i s e d : D e c e m b e r 2 2 , 2 0 2 1 Preventive Maintenance Water Coil Maintenance Condensate Drain (All other water loop applications) In areas where airborne bacteria may produce a “slimy”...
Trilogy Q-Mode (QE) Series IOM - 60Hz HFC-410A ® ® R e v i s e d : D e c e m b e r 2 2 , 2 0 2 1 Troubleshooting Sensor Inputs Table 15: Nominal resistance at various temperatures All sensor inputs are ‘paired wires’...
Page 68
Trilogy Q-Mode (QE) Series IOM - 60Hz HFC-410A ® ® R e v i s e d : D e c e m b e r 2 2 , 2 0 2 1 Table 16: Troubleshooting Code Fault Mode Possible Cause Solution High Discharge Pressure Reduced or no water flow...
Page 69
Trilogy Q-Mode (QE) Series IOM - 60Hz HFC-410A ® ® R e v i s e d : D e c e m b e r 2 2 , 2 0 2 1 Table 16: Troubleshooting (Cont.) Code Fault Mode Possible Cause Solution ECM Low RPM...
Page 70
Trilogy Q-Mode (QE) Series IOM - 60Hz HFC-410A ® ® R e v i s e d : D e c e m b e r 2 2 , 2 0 2 1 Table 16: Troubleshooting (Cont.) Code Fault Mode Possible Cause Solution Low Refrigerant Pressure...
Page 71
Trilogy Q-Mode (QE) Series IOM - 60Hz HFC-410A ® ® R e v i s e d : D e c e m b e r 2 2 , 2 0 2 1 Table 16: Troubleshooting (Cont.) Code Fault Mode Possible Cause Solution DHW Pump Locked Rotor...
Page 72
Trilogy Q-Mode (QE) Series IOM - 60Hz HFC-410A ® ® R e v i s e d : D e c e m b e r 2 2 , 2 0 2 1 Table 16: Troubleshooting (Cont.) Code Fault Mode Possible Cause Solution Reduced HW Setpoint Warning...
Page 73
Trilogy Q-Mode (QE) Series IOM - 60Hz HFC-410A ® ® R e v i s e d : D e c e m b e r 2 2 , 2 0 2 1 Table 16: Troubleshooting (Cont.) Code Fault Mode Possible Cause Solution Low Suction Superheat...
Page 74
Trilogy Q-Mode (QE) Series IOM - 60Hz HFC-410A ® ® R e v i s e d : D e c e m b e r 2 2 , 2 0 2 1 Table 16: Troubleshooting (Cont.) Refrigerant Circuit Diagram Code Fault Mode...
Page 75
Trilogy Q-Mode (QE) Series IOM - 60Hz HFC-410A ® ® R e v i s e d : D e c e m b e r 2 2 , 2 0 2 1 Table 16: Troubleshooting (Cont.) Code Fault Mode Possible Cause Solution Current Sensor Warning...
Page 76
Trilogy Q-Mode (QE) Series IOM - 60Hz HFC-410A ® ® R e v i s e d : D e c e m b e r 2 2 , 2 0 2 1 Table 16: Troubleshooting (Cont.) Code Fault Mode Possible Cause Solution Power Supply Sync Warning...
Page 77
Trilogy Q-Mode (QE) Series IOM - 60Hz HFC-410A ® ® R e v i s e d : D e c e m b e r 2 2 , 2 0 2 1 Table 16: Troubleshooting (Cont.) Code Fault Mode Possible Cause Solution Low Voltage Shutdown...
Page 78
Trilogy Q-Mode (QE) Series IOM - 60Hz HFC-410A ® ® R e v i s e d : D e c e m b e r 2 2 , 2 0 2 1 Table 16: Troubleshooting (Cont.) Code Fault Mode Possible Cause Solution ECM Under Voltage Fault...
Page 79
Trilogy Q-Mode (QE) Series IOM - 60Hz HFC-410A ® ® R e v i s e d : D e c e m b e r 2 2 , 2 0 2 1 Table 16: Troubleshooting (Cont.) Code Fault Mode Possible Cause Solution Loop Flow w/o Loop Pump...
Trilogy Q-Mode (QE) Series IOM - 60Hz HFC-410A ® ® R e v i s e d : D e c e m b e r 2 2 , 2 0 2 1 Refrigeration Troubleshooting Form - Heating Circuit Legend Description Value Notes...
Page 81
Trilogy Q-Mode (QE) Series IOM - 60Hz HFC-410A ® ® R e v i s e d : D e c e m b e r 2 2 , 2 0 2 1 Refrigeration Troubleshooting Form - Heating c l i m a t e m a s t e r . c o m...
Trilogy Q-Mode (QE) Series IOM - 60Hz HFC-410A ® ® R e v i s e d : D e c e m b e r 2 2 , 2 0 2 1 Refrigeration Troubleshooting Form - Cooling Circuit Legend High Pressure Hot Gas Description Value...
Page 83
Trilogy Q-Mode (QE) Series IOM - 60Hz HFC-410A ® ® R e v i s e d : D e c e m b e r 2 2 , 2 0 2 1 Refrigeration Troubleshooting Form - Cooling c l i m a t e m a s t e r . c o m...
Trilogy Q-Mode (QE) Series IOM - 60Hz HFC-410A ® ® R e v i s e d : D e c e m b e r 2 2 , 2 0 2 1 Refrigeration Troubleshooting Form - DHW Circuit Legend Description Value Notes...
Page 85
Trilogy Q-Mode (QE) Series IOM - 60Hz HFC-410A ® ® R e v i s e d : D e c e m b e r 2 2 , 2 0 2 1 Refrigeration Troubleshooting Form - DHW c l i m a t e m a s t e r . c o m...
Trilogy Q-Mode (QE) Series IOM - 60Hz HFC-410A ® ® R e v i s e d : D e c e m b e r 2 2 , 2 0 2 1 Refrigeration Troubleshooting Form - Cooling + DHW Circuit Legend Description Value...
Page 87
Trilogy Q-Mode (QE) Series IOM - 60Hz HFC-410A ® ® R e v i s e d : D e c e m b e r 2 2 , 2 0 2 1 Refrigeration Troubleshooting Form - Cooling + DHW c l i m a t e m a s t e r .
Trilogy Q-Mode (QE) Series IOM - 60Hz HFC-410A ® ® R e v i s e d : D e c e m b e r 2 2 , 2 0 2 1 Warranty G e o t h e r m a l H e a t i n g a n d C o o l i n g...
Page 89
Trilogy Q-Mode (QE) Series IOM - 60Hz HFC-410A ® ® R e v i s e d : D e c e m b e r 2 2 , 2 0 2 1 Notes: c l i m a t e m a s t e r . c o m...
Page 90
Trilogy Q-Mode (QE) Series IOM - 60Hz HFC-410A ® ® R e v i s e d : D e c e m b e r 2 2 , 2 0 2 1 Notes: G e o t h e r m a l H e a t i n g a n d C o o l i n g...
Page 91
Trilogy Q-Mode (QE) Series IOM - 60Hz HFC-410A ® ® R e v i s e d : D e c e m b e r 2 2 , 2 0 2 1 Notes: c l i m a t e m a s t e r . c o m...
97B0112N01 ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time for order may be changed without notice and may not be as described herein. Please contact ClimateMaster’s Customer Service Department at 1-405-745-6000 for specific information on the current design and specifications.