Unit Start-Up And Operating Conditions - ClimateMaster Trilogy Q-Mode (QE) Series Manual

Table of Contents

Advertisement

Unit and System Checkout
BEFORE POWERING SYSTEM, please check the following:
UNIT CHECKOUT
 Shutoff valves: Insure that all isolation valves are open.
 Line voltage and wiring: Verify that voltage is within
an acceptable range for the unit and wiring and fuses/
breakers are properly sized. Verify that low voltage
wiring is complete.
 Unit control transformer: Insure that transformer has
the properly selected voltage tap. Residential 208-
230V units are factory wired for 230V operation unless
specified otherwise.
 Loop/water piping is complete and purged of air. Water/
piping is clean.
 Antifreeze has been added if necessary.
 Entering water and air: Insure that entering water and air
temperatures are within operating limits of Tables 10a
and 10b.
 Ensure that air has been purged from DHW piping and
heat exchanger and that DHW pump unions are tight.
 Low water temperature cutout: Verify that low water
temperature cut-out is properly set.
 Unit fan: Manually rotate fan to verify free rotation and
insure that blower wheel is secured to the motor shaft.
Be sure to remove any shipping supports if needed. DO
NOT oil motors upon start-up. Fan motors are pre-oiled
at the factory. Check unit fan CFM selection and compare
to design requirements.
 Condensate line: Verify that condensate trap is installed
and pitched.
 Unit air coil and filters: Insure that filter is clean and
accessible. Clean air coil of all manufacturing oils.
 Unit controls: Verify that EXM field selection options are
properly configured. Low voltage wiring is complete.
 Blower CFM and Water ∆T are properly configured.
 Service/access panels are in place.
SYSTEM CHECKOUT
 System water temperature: Check water temperature
for proper range and also verify heating and cooling set
points for proper operation.
 System pH: Check and adjust water pH if necessary to
maintain a level between 6 and 8.5. Proper pH promotes
system longevity (see Table 5).
 System flushing: Verify that all air is purged from the
system. Air in the system can cause poor operation or
system corrosion. Water used in the system must be
potable quality initially and clean of dirt, piping slag,
and strong chemical cleaning agents. Some antifreeze
solutions may require distilled water.
 Internal Flow Controller: Verify that it is purged of air and
in operating condition.
 System controls: Verify that system controls function and
operate in the proper sequence.
 Low water temperature cutout: Verify that low water
temperature setting is appropriate for the application.
 Miscellaneous: Note any questionable aspects of
the installation.
Trilogy
Q-Mode
(QE) Series IOM - 60Hz HFC-410A
®
®

Unit Start-Up and Operating Conditions

CAUTION! Verify that ALL water valves are open and
allow water flow prior to engaging the compressor. Freez-
ing of the heat exchanger or water lines can permanently
damage the heat pump.
CAUTION! To avoid equipment damage, DO NOT
leave system filled in a building without heat during the
winter unless antifreeze is added to the water loop. Heat
exchangers (including the DHW heat exchanger) never
fully drain by themselves and will freeze unless winterized
with antifreeze.
Unit Start-up Procedure
1.
Ensure all valves are adjusted to their full open position.
Ensure line power to the heat pump is on.
2.
Room temperature should be within the minimum-
maximum ranges of listed in the unit IOM. During start-
up checks, loop water temperature entering the heat
pump should be between 30°F [-1°C] and 95°F [35°C].
3.
It is recommended that Trilogy Q-Mode
started in the hot water mode, when possible. This will
allow liquid refrigerant to flow through the filter-drier
before entering the EEV, allowing the filter-drier to catch
any debris that might be in the system before it reaches
the EEV. It will also warm the water in the hot water
heat exchanger, preventing liquid refrigerant migration
to the heat exchanger.
Place the unit in Hot Water Operational mode through
the Manual Operation setting with the myUplink Pro
app or Service Tool.
a.
The manual mode with energize the Loop Pump
Speed and the DHW Pump Speed to default values.
b.
Check for vibration, noise, and water leaks.
c.
Verify that the compressor is on and that the hot
water temperature rise is within normal range.
Allow the unit to run long enough to heat the water
tank to at least 90°F.
NOTE: Allow three (3) minutes between tests for pressure to
equalize before beginning heating test.
5.
While still in the manual operation mode, turn on the
blower by setting the ECM Target Airflow to a nominal
amount.
a. Verify the blower is running and that air is moving
appropriately through the duct system.
b. Verify that the loop pump is running.
c.
Set the unit operating mode to Heating Set the unit
manual operating mode to Heating.
NOTE: The compressor will not start if the blower
and pump are not operating at appropriate levels.
d. Check for vibration, noise, and water leaks
c l i m a t e m a s t e r . c o m
R e v i s e d : D e c e m b e r 2 2 , 2 0 2 1
CAUTION!
CAUTION!
units be first
®
45

Advertisement

Table of Contents
loading

Table of Contents