Electrical - Line Voltage - ClimateMaster Trilogy Q-Mode (QE) Series Manual

Table of Contents

Advertisement

WARNING!
WARNING! To avoid possible injury or death due to
electrical shock, open the power supply disconnect switch
and secure it in an open position during installation.
CAUTION!
CAUTION! Use only copper conductors for field installed
electrical wiring. Unit terminals are not designed to accept
other types of conductors.
Table 7: Trilogy
(QE) Series ECM with Internal Flow Controller
®
Electrical Data
Compressor
QE
Rated
Model
Voltage
RLA
LRA
0930 208/230/60/1 20.0
20.0
1860 208/230/60/1 32.0
32.0
Rated Voltage of 208/230/60/1
HACR circuit breaker in USA only
WARNING!
WARNING! Disconnect electrical power source to
prevent injury or death from electrical shock. The
capacitors on the inverter board store electrical energy.
They will remain charged long after power has been
disconnected. Extreme care should be used when
working around these capacitors.
CAUTION!
CAUTION! Use only copper conductors for field installed
electrical wiring. Unit terminals are not designed to accept
other types of conductors.

Electrical - Line Voltage

All field installed wiring, including electrical ground, must
comply with the National Electrical Code as well as all
applicable local codes. Refer to the unit electrical data for fuse
sizes. Consult wiring diagram for field connections that must
be made by the installing (or electrical) contractor.
All final electrical connections must be made with a length of
flexible conduit to minimize vibration and sound transmission
to the building.
General Line Voltage Wiring
Be sure the available power is the same voltage and phase
shown on the unit serial plate. Line and low voltage wiring
must be done in accordance with local codes or the National
Electric Code, whichever is applicable.
Trilogy
®
HW
Ext
Fan
Total
Min
Pump
Loop
Motor
Unit
Circ
FLA
FLA
FLA
FLA
Amp
0.5
1.44
3.9
25.3 30.3
0.5
1.44
6.9
40.3 48.3
Min/Max Voltage of 197/254
All fuses Class RK-5
c l i m a t e m a s t e r . c o m
Q-Mode
(QE) Series IOM - 60Hz HFC-410A
®
Electrical - Line Voltage
Figure 19: Trilogy Unit with Mitsubishi Inverter
Max
Fuse/
HACR
50
80
(see electrical table 7 for minimum circuit
amps and maximum breaker size)
R e v i s e d : D e c e m b e r 2 2 , 2 0 2 1
Unit Power Supply