9. Troubleshooting
NOTE
Before grid connection, if the string has negative current, it means the
voltage between the two strings of one MPPT is unbalanced.
One of two string may have more PV panels than another one.
NOTE
If the inverter displays any alarm message as listed in Table 9.1; please
turn off the inverter (refer to Section 6.2 to stop your inverter) and wait for 15
minutes before restarting it (refer to Section 6.1 to start your inverter). If the
failure persists, please contact your local distributor or the service center.
Please keep ready with you the following information before contacting us.
1. Serial number of Canadian Solar Three Phase Inverter;
2. The distributor/dealer of Canadian Solar Three Phase Inverter (if available);
3. Installation date.
4. The description of problem (i.e. the alarm message displayed on the LCD and the status
of the LED status indicator lights. Other readings obtained from the Information submenu
(refer to Section 6.2) will also be helpful.);
5. The PV array configuration (e.g. number of panels, capacity of panels,
number of strings, etc.);
6. Your contact details.
.62.

10. Specifications

Model
Max. DC input voltage (Volts)
Rated DC voltage (Volts)
Start-up voltage (Volts)
MPPT voltage range (Volts)
Full load MPPT voltage range (Volts)
Max. input current (Amps)
Max short circuit input current (Amps)
MPPT number/Max input strings number
Rated output power (Watts)
Max. output power (Watts)
Max. apparent output power (VA)
Rated grid voltage (Volts)
Rated output current (Amps)
Power Factor (at rated output power)
THDi (at rated output power)
Rated grid frequency (Hertz)
Max.efficiency
EU efficiency
Dimensions (W*H*D)
Weight
Topology
Self consumption (night)
Operating ambient temperature range
Storage environment
Relative humidity
Ingress protection
Noise emission
Cooling concept
Max.operation altitude
Compliance
DC connection
AC connection
Display
Communication connections
Warranty
CSI-185K-T600GL02-U
1500
950
500
480...1500
860...1300
14*26
14*40
14/28
185000
185000
185000
3/PE~600
178.0
>0.99 (0.8 leading - 0.8 lagging)
<3%(at rated output power)
60
99.0%
98.5%
1170*770*384 (mm) / 46.1*30.3*15.1 (inch)
113kg / 249lbs
Transformerless
<2W
°F
°C
-13...140
/ -25...+60
°F
°C
-40...176
/ -40...+80
0~100%
Type 4X
≤65dB(A)
Intelligent redundant cooling
13120ft / 4000m
UL 1741, UL 1741SA, UL 1998, UL 1699B,
IEEE 1547, FCC Part 15 (Class A & B),
CAN/CSA C22.2 107.1-1,
California Rule 21 Phaes II & III
MC4 connectors
OT Terminal connectors(Max.300mm²)
LCD,2x20Z
RS485, Optional: PLC
5 years standard (extend to 20 years)