Notice For Use; Protection Circuitry And Controls; Installation; Environmental Considerations - CanadianSolar CSI-185K-T600GL03-U Installation And Operation Manual

Csi grid-tied pv inverter
Table of Contents

Advertisement

2. Safety Instructions
CAUTION
Risk of electric shock from energy stored in the inverter's capacitors.
Do not remove cover until five (5) minutes after disconnecting all sources
of supply have passed, and this can only be done by a service technician.
The warranty may be voided if any unauthorized removal of cover occurs.

2.3 Notice for Use

The inverter has been constructed according to applicable safety and technical guidelines.
Use the inverter in installations that meet the following requirements ONLY:
1). The inverter must be permanently installed.
2). The electrical installation must meet all the applicable regulations and standards.
3). The inverter must be installed according to the instructions stated in this manual.
4). The system design must meet inverter specifications.
To start-up the inverter, the Grid Supply Main Switch (AC) must be turned on, BEFORE the DC
Switch is turned on. To stop the inverter, the Grid Supply Main Switch (AC) must be turned off
before the DC Switch is turned off.

2.4 Protection Circuitry and Controls

To meet relevant codes and standards, the Canadian Solar U.S. three phase inverter line is
equipped with protective circuitry and controls. These include Arc Fault Circuit Interrupter
(AFCI) and Anti-Islanding Protection.
Arc Fault Circuit Interrupter AFCI:
Edition 2011 of the National Electrical Code®, Section 690.11, requires that all PV plants
attached to a building are fitted with a means of detecting and interrupting serial electric
arcs in the PV wiring and array. An electric arc with a power of 300W or greater must be
interrupted by the AFCI in the time specified by UL 1699B. A triggered AFCI fault may only
be reset manually. After clearing the source of the fault, the AFCI can be deactivated via
the inverter front panel interface.
Anti-Islanding Protection:
Islanding is a condition where the inverter continues to produce power even when the grid
is not present. Circuitry, along with firmware, has been designed to determine if the grid is
present by adjusting the output frequency of the inverter. In the case of a 60Hz resonant
system where the inverter is partially isolated from the grid, the inverter programming can
detect if there is a resonant condition or if the grid is actually present. It can also
differentiate between inverters operating in parallel and the grid.
.8.

3.1 Environmental considerations

3.1.1 Select a location for the inverter

When selecting a location for the inverter, consider the following:
WARNING: Risk of fire
Despite careful construction, electrical devices can cause fires.
Do not install the inverter in areas containing highly flammable materials or
gases.
Do not install the inverter in potentially explosive atmospheres.
● The temperature of the inverter heat-sink can reach 167°F(75℃).
● The inverter is designed to work in an ambient temperature range between -25~140°F(-32~60℃).
● If multiple inverters are installed on site, a minimum clearance of 27.5 in should be kept
between each inverter and all other mounted equipment. The bottom of the inverter should be
at least 27.5 in above of the ground or floor (see Figure 3.1).
● The LED status indicator lights and the LCD located on the inverter's front panel should not be
blocked.
● Adequate ventilation must be present if the inverter is to be installed in a confined space.
27.5in
Figure 3.1 Distances required between inverters
NOTE
Nothing should be stored on or placed against the inverter.

3. Installation

27.5in
27.5in
27.5in
.9.

Advertisement

Table of Contents
loading

Table of Contents