Grid On/Off - CanadianSolar CSI-185K-T600GL03-U Installation And Operation Manual

Csi grid-tied pv inverter
Table of Contents

Advertisement

7. Normal operation
Setting value
600V Rated (L-L)
600V Rated (L-N)
Vup-Limit1
660<V<720
Time1
1S
Vup-Limit2
V≥720
Time2
0 16S
.
Vdw-Limit1
360≤V<528
Time1
2S
Vdw-Limit2
V<360
Time2
0 16S
.
Fup-Limit1
60.5Hz<F<62Hz
60.5Hz<F<62Hz
Time1
2S
Fup-Limit2
F> 2Hz
6
Time2
0 16S
.
Fdw-Limit1
57Hz<F<59.5Hz
57Hz<F<59.5Hz
Time1
2S
Fdw-Limit2
57Hz<F
Time2
0 16S
.
Table 7.2 Baseline Inverter Settings
OV-G-V1: 300---480V
OV-G-V1-T: 0.01---9.00S
OV-G-V2: 300---490V
OV-G-V2-T: 0.01---9.00S
UN-G-V1: 173---336V
UN-G-V1-T: 0.01---9.00S
UN-G-V2: 132---319V
UN-G-V2-T: 0.01---9.00S
Startup-T: 10-600S
Table 7.3 Setting ranges for User-Def (600V for 185K)
.38.
800V Rated (L-L)
800V Rated (L-N)
381<V<415
880<V<960
508<V<553
1S
1S
V≥415
V≥960
0 16S
.
0 16S
.
207≤V<304
480≤V<704
276≤V<405
2S
2S
V<207
V<480
0 16S
.
0 16S
.
60.5Hz<F<62Hz
60.5Hz<F<62Hz
2S
2S
F> 2Hz
6
F> 2Hz
6
F> 2Hz
0 16S
.
0 16S
.
57Hz<F<59.5Hz
57Hz<F<59.5Hz
2S
2S
57Hz<F
57Hz<F
57Hz<F
0 16S
.
0 16S
.
OV-G-F1: 50.2-63Hz
OV-G-F1-T: 0.01---9.00S
OV-G-F2: 51-63Hz
OV-G-F2-T: 0.01---9.00S
UN-G-F1: 47-59.5Hz
UN-G-F1-T: 0.01---9.00S
UN-G-F2: 47-59Hz
UN-G-F2-T: 0.01---9.00S
Restore-T: 10-600S
OV-G-V1: 700---900V
OV-G-V1-T: 0.1---300S
OV-G-V2: 700---900V
1S
OV-G-V2-T: 0.1---300S
V≥553
UN-G-V1: 500---800V
0 16S
.
UN-G-V1-T: 0.1---300S
UN-G-V2: 500---800V
2S
UN-G-V2-T: 0.1---300S
V<276
Startup-T: 10-600S
0 16S
.
2S
6
0 16S
.
2S
7.5.2 Switch ON/OFF

7.5.2.1 Grid ON/OFF

0 16S
.
This function is used to start up or stop the power generation of Canadian Solar Inverter.
Screens can be scrolled manually by pressing the UP/DOWN keys. Press the ENTER key
to save the setting. Press the ESC key to return to the previous menu.
7.5.2.2 24H-VarSwitch
This function is used to disable or enable the reactive power compensation at night.
Press UP/DOWN to select and press to Enter to save the setting.
Press the ESC to return to the previous menu.
7. Normal operation
OV-G-F1: 50.1-65Hz
OV-G-F1-T: 0.1---300S
OV-G-F2: 50.1-65Hz
OV-G-F2-T: 0.1---300S
UN-G-F1: 45-59.9Hz
UN-G-F1-T: 0.1---300S
UN-G-F2: 45-59.9Hz
UN-G-F2-T: 0.1---300S
Restore-T: 10-600S
Table 7.4 Setting ranges for User-Def (800V for 255K)
NOTE
The initial value of the User-Def standard is for reference only. It does
not represent a correct value suitable for use.
Grid ON
Grid OFF
Figure 7.18 Set Grid ON/OFF
Enable
Disable
Figure 7.19 Set 24H-Var Switch