7. Normal operation

7.4.6 Yearly Energy

The function is for checking the energy generation for selected year.
YES=<ENT> NO=<ESC>
Figure 7.12 Select year for yearly energy
Press DOWN key to move the cursor to day and year, press UP key to change the digit.
Press Enter after the date is fixed.
2020: 0000000kWh
2019: 0000000kWh
Figure 7.13 Yearly energy
Press UP/DOWN key to move one date from another.

7.4.7 Daily Records

The screen shows history of changing settings. Only for maintance personel.

7.4.8 Communication Data

The screen shows the internal data of the Inverter (see Figure 7.14), which is for service
technicians only.
01-05: 01 25 E4 9D AA
06-10: C2 B5 E4 9D 55
Figure 7.14 Communication Data

7.4.9 Warning Message

The display shows the
100
latest warn messages (see Figure 7.15). Screens can be scrolled
manually by pressing the UP/ DOWN keys. Press the ESC key to return to the previous menu.
Msg000:
T: 00-00 00:00 D:0000
Figure 7.15 Warning Message
.36.
Select:
2020
7. Normal operation

7.5 Advanced Settings - Technicians Only

NOTE:
To access to this area is for fully qualified and accredited technicians only.
Please follow 7.4 to enter password to access this menu.
Select Advanced Settings from the Main Menu to access the following options:
1. Select Standard
2. Switch ON/OFF
3. Clear Energy
4. Reset Password
5. Power Control
6. Calibrate Energy
7. Special Settings
8. STD. Mode Settings
9.Restore Settings
10. HMI Update
11. Restart HMI
12. Fan Test
13. DSP Update
14. Compensation Set
15. I/V Curve

7.5.1 Selecting Standard

This function is used to select the grid's reference standard.
Selecting the "User-Def" menu will access to the following submenu.
YES=<ENT> NO=<ESC>
Standard:UL-600V
Figure 7.16 UL-600V
YES=<ENT> NO=<ESC>
Standard:UL-800V
Figure 7.17 UL-800V
Below is the setting range for "User-Def". Using this function, the limits can be changed
manually. (These voltage values are the phase voltage)
OV-G-V1: 660V
OV-G-V1-T: 0.6S
OV-G-V1: 880V
OV-G-V1-T: 0.6S