13 Parameters of the unit

Model
Power system
Type
Outline
Body
dimension
(WxDxH)
Panel
If there is any change,we will not give you notice here, the correct parameters is in the
nameplate of your FCU
The FCU designed for installation indoor. The environmental temperature is from 5°C to 43°C,
water working temperature is from 7°C to 60°C.
The A-weighted sound pressure level is below 70dB.
The temperature exchange efficiency and enthalpy exchange efficiency are tested under these
testing conditions as below:
1) Cooling capacity: air 27°C DB , 19°C WB, water temperature intake 7°C, outlet 12°C.
2) Heating capacity: air 20°C DB , Water temperature intake 50°C, outlet 40°C.
3) Freeze-up : air 27°C DB, 24°C WB , water temperature 6°C intake , 10°C outlet .
4) Sound power level according to ISO 5151. Sound pressure level are calculated at the below
of air-outlet 1m and 1m distance. The noise are tested before leaving factory.
FP-85XD/B-T
FP-85XDS/B-T
FP-85XDM/B-T
FP-85XDSM/B-T
FP-102XD/B-T
FP-102XDS/B-T
FP-102XDM/B-T
FP-102XDSM/B-T
V-Ph-Hz
220-240V-1Ph~50Hz、208-230V-1Ph~60Hz
mm
840x840x190
mm
950x950x85
20
Cassette Type Fan Coil Unit
FP-125XD/B-T
FP-180XD/B-T
FP-125XDS/B-T
FP-180XDS/B-T
FP-125XDM/B-T
FP-180XDM/B-T
FP-125XDSM/B-T
FP-180XDSM/B-T
FP-140XD/B-T
FP-200XD/B-T
FP-140XDS/B-T
FP-200XDS/B-T
FP-140XDM/B-T
FP-200XDM/B-T
FP-140XDSM/B-T
FP-200XDSM/B-T
FP-160XD/B-T
FP-160XDS/B-T
FP-160XDM/B-T
FP-160XDSM/B-T
840x840x240
950x950x85
840x840x320
950x950x85

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents