Performance Parameters Of The Unit - Gree GMV-Pdhm224W/Na-M Installation And Operating Instruction Manual

Heat recovery d.c inverter multi vrf
Hide thumbs Also See for GMV-Pdhm224W/Na-M:
Table of Contents

Advertisement

Performance Parameters of the Unit

Remarks:
1. All the data of the cooling/heating capacity and the noise are measured before the unit is shipped out from
manufacturer.
2. All the parameters in the tables below are measured under the rated work condition. Such parameters in the
specifications are subject to change so the data on the nameplate shall govern.
● Performance Parameters of the Outdoor Unit
Basic Model
Power Supply
Cooling
Capacity
Heating
Cooling
Power
Input
Heating
Cooling
COP
Heating
Cooling &
ECOP
Heating
Capacity Control
Type
Compressor
NO.
Air Flow Rate
Dimensions ( H×W×D )
Package Dimensions
( H×W×D )
Net Weight
Gross Weight
Sound Pressure Level
Type
Refrigerant
Charge
Refrigerant Oil
Liquid
Suction
Piping
Gas
Connections
Discharge
Gas
Number of Max.
Connectable Indoor Unit
Ratio of the Connectable
Indoor Unit
Recommended Power
Cord
GMV-Pdhm224W/Na-M
22.4
kW
76,428.8
Btu/h
25.0
kW
85,300.0
Btu/h
5.5
kW
5.8
kW
4.07
W/W
4.31
W/W
W/W
20~100
%
3
m
/min
mm
mm
260
kg
284
kg
58
dB(A)
12.0
kg
Φ9.5
mm
mm
Φ22.2
mm
Φ19.1
13
2
mm
×NO.
6.0×5
GMV-Pdhm280W/Na-M
3phase,380~415V,50HZ,4wires system
95,536.0
95,536.0
6.8
Hermetically sealed scroll type
2
190
1670×930×770
1850×1010×850
Refer to the nameplate of the compressor
50%~135%
81
GMV-Pdhm335W/Na-M
28.0
31.5
7.5
7.7
3.73
4.09
14~100
2
1850×1420×850
260
284
58
R410A
12.0
Φ9.5
Φ22.2
Φ19.1
16
6.0×5
33.5
114,302.0
37.5
114,302.0
9.23
9.38
3.63
4.00
6.5
14~100
3
232
1670×1340×770
372
390
61
14.0
Φ12.7
Φ28.6
Φ19.1
19
10.0×5

Advertisement

Table of Contents
loading

Table of Contents