Initial Power-On Procedures; Power-On Self-Test And Heater Time Delay - CPI 0102324500rR Manual

Table of Contents

Advertisement

4.4 Initial Power-On Procedures

Initial power-on procedures for the CHPA should not be attempted until all pre-power
procedures have been completed. This task should be performed by a qualified operator only;
this is not a normal power-on sequence. Should a fault or maladjustment be discovered during
initial power-on, turn to Chapter 5, "Operation," for help in diagnosis; or contact CPI customer
support (for telephone number see Appendix A). Initial power-on and checkout are to be
performed in the following order:
POST (Power-On Self-Test) and HTD (Heater Time Delay) countdown
Verification of operational settings, which include fault and alarm trip settings
Verification of serial port settings
Verification of RF output level
Each phase of checkout is described in the paragraphs that follow.
4.4.1

Power-On Self-Test and Heater Time Delay

Each time the CHPA power is switched on, the microprocessor controller performs a series of
self-tests to ensure that it has the ability to control and monitor the CHPA. The HTD (Heater
Time Delay) then counts down for a predetermined time to allow the TWT (traveling wave
tube) heater to warm up. The following steps are to be performed in the order indicated. Refer
to "Basic CHPA Operations" in Chapter 5 for example displays during each operating state.
Verify the response of the CHPA during each step:
1. Switch on AC power to the CHPA; the AC power switch is located on the front panel on the
front of the unit. (Self-tests begin at this time.)
Note: Repeated cycling of AC power (more than 3 times per minute or 8
times per minute or 8 times per 5 minute period) will result in excessive
inrush current and may trip circuit breaker.
If a self-test fails, the error is reported on the front panel display. (Refer to Chapter 5,
"Operation," for further steps if this occurs.)
2. The display will then light to indicate that the self-tests passed. Look for the following:
HTD countdown starts at 3:00 minutes and counts down to 0 minutes.
During countdown, verify that LOCAL is indicated in the upper left corner of the
display. If it is not, press the LCL/RMT pushbutton until it does light. (This indicates
that the front panel has complete control of the CHPA.)
If XMIT SELECT is shown on the display, press the TRANSMIT/STANDBY pushbutton
until the XMIT SELECT is no longer shown. (This action will prevent the CHPA from
transitioning to the Transmit state at the conclusion of HTD.)
If a fault occurs during this countdown period, the FAULT LED will light and the
display will indicate the fault. (Refer to Chapter 5, "Operation," under "Fault State.")
D
.01023245 R
.R
OC
EV
THIS DOCUMENT IS THE PROPERTY OF COMMUNICATIONS & POWER INDUSTRIES.
REPRODUCTION OR RELEASE WITHOUT EXPRESS PERMISSION IS STRICTLY PROHIBITED
CHPA S
ERIES
4-3

Advertisement

Table of Contents
loading

Table of Contents