Panasonic WH-MXC09J3E8 Service Manual page 163

Air-to-water heatpump
Hide thumbs Also See for WH-MXC09J3E8:
Table of Contents

Advertisement

17.5.14 Outdoor High Pressure Abnormality (H64)
Malfunction Decision Conditions:
During operation of cooling and heating, when the outdoor high pressure sensor output signal is 0 Vdc or 5 Vdc.
Malfunction Caused:
1
Faulty connector connection.
2
Faulty sensor.
3
Faulty outdoor unit PCB (main).
Abnormality Judgment:
Continue 4 times in 20 minutes.
Troubleshooting:
Check the CN-HPS connector connection:
- Turn OFF the power
- Check the connector connection
Is the CN-HPS connector
connection normal?
Yes
Check the continuity of the outdoor unit PCB (main)
high pressure sensor connector CN-HPS:
- Plug out connector from the outdoor unit PCB (main)
- Measure the continuity pin 1 & 3 (GND) and pin 1 &
4 (5 V) of CN-HPS
Is there any continuity?
Caution
No
- Connector poor contact
- Correct the connection
- Detect in outdoor unit
Yes
PCB (main)
- Replace the outdoor
unit PCB (main)
No
For safety reason and to prevent component breakdown,
always switch off the power before remove and connect the component.
Reconnect the high pressure sensor
connector to the outdoor unit PCB (main).
Turn ON the power and run the system.
Measure the DC voltage pin 1 & 3 (GND)
of CN-HPS.
Is the measured voltage
0 Vdc or 5 Vdc?
163
- Defect in outdoor unit
No
PCB (main)
- Replace the outdoor
unit PCB (main)
Yes
- Defect in outdoor high
pressure sensor
- Replace the outdoor
high pressure sensor

Hide quick links: