17.5.16 Abnormal External Thermistor 1 (H67)
Malfunction Caused:
1
Faulty connector connection.
2
Faulty room temperature zone 1 sensor.
3
Faulty indoor sub PCB.
Abnormality Judgment:
Continue for 5 seconds.
Abnormal external thermistor 1
Check CN205 connector on sub PCB normal?
Disconnect sensor from sub PCB measure resistance of sensor
and compare against sensor characteristic same?
Change sub PCB
YES
YES
Caution
NO
●
Correct connection
NO
●
Change external thermistor 1
165
For safety reason and to prevent
component breakdown, always switch
off the power before remove and