16.1.4
Specifications
16.1.4.1
Specifications of Fresh Water was Heat Transfer Medium in Brazed Heat
Exchanger
Parameter
Quality Limits for Tap Water on the Secondary Side
Temperature
Below 60°C
pH
7 to 9
Alkalinity
60mg/I <HCO
Conductivity
< 500μS/cm
Hardness
[Ca
Chloride
< 200mg/l at 60°C
Sulphate
[SO
Nitrate
NO
Chlorine
< 0.5mg/l
16.1.4.2
External Filter
Solids in the water must be filtered.
Minimum filter mesh size required for the field supply external filter in the water inlet is 20 mesh.
<300mg/I
3
+
, Mg
+
] / [HCO
-
] > 5
3
2-
] > 100mg/I and [HCO
4
< 100mg/I
3
-
2-
] / [SO
] > 1
3
4
143