Panasonic WH-MXC09J3E8 Service Manual page 71

Air-to-water heatpump
Hide thumbs Also See for WH-MXC09J3E8:
Table of Contents

Advertisement

Boiler connection
Mono bloc
This is an application that connects the boiler to the Mono bloc, to compensate for insufficient capacity by operate
boiler when outdoor temperature drops & heat pump capacity is insufficient.
Boiler is connected parallel with heat pump against heating circuit.
There are 3 modes selectable by remote controller for boiler connection.
Besides that, an application that connects to the DHW tank's circuit to heat up tank's hot water is also possible.
(Operation setting of boiler shall be responsible by installer.)
This system requires optional PCB (CZ-NS4P).
Depending on the settings of the boiler, it is recommended to install buffer tank as temperature of circulating water
may get higher. (It must connect to buffer tank especially when selecting Advanced Parallel setting.)
Panasonic is NOT responsible for incorrect or unsafe situation of the boiler system.
Make sure the boiler and its integration in the system complies with applicable legislation.
Make sure the return water temperature from the heating circuit to the Mono bloc does NOT exceed 55°C.
Boiler is turned off by safety control when the water temperature of the heating circuit exceed 85°C.
Buffer tank
Mixing
Pump
valve
Boiler
Setting of remote controller
Installer setting
Thermistor
Floor heating
WARNING
CAUTION
71
System setup
Optional PCB connectivity - Yes
Bivalent - Yes
Turn ON: outdoor temp
Control pattern

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Wh-mxc12j9e8

Table of Contents