Panasonic WH-MXC09J3E8 Service Manual page 89

Air-to-water heatpump
Hide thumbs Also See for WH-MXC09J3E8:
Table of Contents

Advertisement

13.1.4
Target Water Temperature Setting
13.1.4.1
Target Water Temperature Control of Standard System (Optional PCB not
connected)
There are 2 types of temperature control selection which are Compensation and Direct.
Temperature control type selection by installer:
1
Compensation : WLo, WHi, ODLo, ODHi can be set at installer menu.
2
Direct
Remote control setting by user:
1
Compensation : Shift value ±5°C from the compensation curve
2
Direct
*This setting is only able to set when the room sensor select as Water Temperature.
*Instead of water temperature, user will set target room temperature when room sensor select as Room Thermistor
OR Internal Room Thermostat.
Target water temperature is calculated as below condition.
Target water temperature = A (Base temperature) + B (shift temperature)
o
A (Base Temperature)
B (shift temperature) value is depend on the room sensor selection at remote controller as below table:
o
B (Shift Temp.)
Water temperature
External Room thermostat
Internal Room Thermostat &
Room Thermistor
Maximum/minimum regulation of Target Water Temperature.
1
*
Between outdoor ambient -15°C and -20°C, the water outlet temperature gradually decreases from 60°C to 55°C.
*
1
Between outdoor ambient 5°C and 0°C, the water outlet temperature gradually decreases from 65°C to 60°C.
1
*
Between outdoor ambient 20°C and 25°C, the water outlet temperature gradually decreases from 65°C to 60°C.
*
2
Only when ΔT is set to 15°C, the set temperature above 60°C will take effect.
: Direct Water Temperature Set
: Direct water temperature set change
Compensation
Value from the curve + User shift value set
B shift value depend on the room sensor selection at remocon as table below
B = 0
B = 0
Cool Mode:
B = 0 ; when Zone OFF or Zone Room Thermo OFF
B = 1* (room set temp (R/C) - actual room temp)
Max/Min Regulation of B: (Max = 5 ; Min = -5)
Heat Mode:
B = 0 ; when Zone OFF or Zone Room Thermo OFF
B = follow Heating PI control contents
Max
60 (Ambient -15 ~ 0°C or Above Ambient 25°C) *
Min
Sensor selection
Heating
1
55 (Below Ambient -20°C) *
65 (Ambient 5 ~ 20°C) *
1
*
2
20°C
89
Direct
Direct value from user setting
Cooling
1
20°C
5°C