17.5.17 Abnormal External Thermistor 2 (H68)
Malfunction Caused:
1
Faulty connector connection.
2
Faulty room temperature zone 2 sensor.
3
Faulty indoor sub PCB.
Abnormality Judgment:
Continue for 5 seconds.
Abnormal external thermistor 2
Check connector CN205 on sub PCB normal?
Check resistance of external thermistor 2 compare against
characteristic of external thermistor same?
Change sub PCB
YES
YES
Caution
NO
Correct external thermistor 2 sensor
connector
NO
Change external thermistor 2
166
For safety reason and to prevent
component breakdown, always switch
off the power before remove and
connect the component.