3.10.3 Chartless code display function

The chartless code represents the coded inside air temperature.
Select "ON" of the chartless code setting to indicate the code on the LED.
For the chartless code setting, refer to the "optional conditions setting" on the page 3-30.
P code: Indicates the pull-down time.
H code: Indicates the abnormal temperature records.
d code: Indicates the operation history.

3.10.3.1 List of chartless code

C: chilled mode, F: Frozen mode, PF: Partial frozen mode
Code
The alarm is displayed when the control temperature does not decrease by
H001
3˚C
or more for every 4 hours during pull-down operation.
The alarm is displayed when the total out-of- in-range reaches 2 hours.
H002
(Count is not performed during defrosting.)
The alarm is displayed when the integrated time of state "below SP-1˚C"
H003
reaches 2 hours.
The alarm is displayed when the integrated time of state "below SP-2˚C"
H004
reaches 2 hours.
The alarm is displayed when the control air temperature is Out-of -In-
H005
Range and defrosting was performed successively three times while the
control air temperature does not return to in-range.
The alarm is displayed when the integrated time of difference 2 ˚C or more
H006
between control sensor data and record sensor data reaches to one hour
or more.
When the total time above set point +3˚C reaches 1 hour , the code
d3XX
"d301" will be displayed.
When the total time above set point +2˚C reaches 1 hour , the code
d2XX
"d201" will be displayed.
When the total time above set point +1˚C reaches 1 hour , the code
d1XX
"d101" will be displayed.
When the total time below set point –1˚C reaches 1 hour , the code
d–1X
"d-11" will be displayed.
When the total time below set point –2˚C reaches 1 hour , the code
d–2X
"d-21" will be displayed.
XXX: When the total pull-down time reaches one hour, an indication
PXXX
XXX=001 appears.
Note 1) The encircled setting can be changed.
Note 2) To delete the H code or d code, press the
relevant code indicated.
Note 3) H code and d code are deleted when turn off the power supply for 3 days.
Description
key for 3 seconds during the
3-59
Operation mode Figure
C, F, PF
2
C, F, PF
3
C
4
C
4
C, F, PF
5
C, F, PF
6
C, F, PF
7
C, F, PF
7
C, F, PF
7
C, F, PF
7
C, F, PF
7
C, F, PF
1