Page 3
3/105 | S-BM2 Smoke Control Damper - MA multi Description Smoke control dampers are designed for mechanical or natural smoke and heat extract systems. Its function is to extract toxic gases, smoke and fire or provide a supply of fresh air to fire compartments. Smoke control dampers are fitted with an actuator without a spring;...
Page 4
4/105 | S-BM2 Accessories Detailed information about accessories is available in design.systemair.com • K1-S-BM2: Cover boards for in-duct installation. • H1-S-BM2: Hanger for horizontal damper mounting. Design S-BM2 has a casing and blades made from calcium silicate board. The closed damper is sealed by silicate wool sealing to avoid the spread of heat and smoke.
5/105 | S-BM2 Technical Parameters Durability Test 10000 cycles, actuator controlled (0 … 90 degrees rotation) – with no change of the required properties 10000 cycles, actuator controlled for "MOD" classification (45 ... 60 degrees rotation) - with no change of the required properties Testing Pressure Underpressure up to 300 Pa, overpressure up to 1000 Pa...
Page 6
6/105 | S-BM2 Allowed Pressure 1000 Pa Blade Tightness (EN 1751) Class 3 as standard Tightness of the Housing (EN 1751) Class C as standard Conformity with EC Directives 2006/42/ES Machinery Directive 2014/35/EU Low Voltage Directive 2014/30/EU Electromagnetic Compatibility Directive Driving Actuator Types Belimo BEN24, BEN230, BEN24-ST, BEN24-SR;...
Page 7
7/105 | S-BM2 Product Parts The S-BM2 packaging for selected sizes also includes wooden manipulation jig. Legend: P1 - Damper casing P2 - Damper blade P3 - Actuator P4 - Supply and communication unit (BST) P5 - Sheet metal Grille P6 - Threaded inserts for duct connection P7 - Threaded inserts for the grille P8 - Mechanism cover...
Page 8
8/105 | S-BM2 Assessed Performance 19 CE 1396 Systemair Production a.s. 90043 Kalinkovo 371, Slovakia 1396-CPR-0157 EN 12101-8:2011 Smoke control damper Multi compartment S-BM2 Nominal activation conditions/sensitivity • Manual intervention - passed Closure/opening during test at correct time and in allowable time...
9/105 | S-BM2 Diagrams of S-BM2 for extract air Accessories K1-S-BM2 and H1-S-BM2 do not affect the pressure drop and A-weighted total discharged sound power level. The pressure drop and A-weighted total discharged sound power level depend on the nominal width and height of the S-BM2 and air flow volume at different duct pressures.
Page 10
10/105 | S-BM2 S-BM2-...-11- S-BM2-...-11- Pressure drop & A-weighted sound power level in dB(A) Pressure drop & A-weighted sound power level in dB(A) 1000 1000 5000 10000 95 100 W: 125, H: 325 W: 500, H: 625 85 90 W: 300, H: 425 W: 800, H: 825 W: 200, H: 325 W: 1000, H: 1225...
Page 11
11/105 | S-BM2 S-BM2 Grille Types M0, M1 - 2 dampers vertically assembled into battery S-BM2-...-M0- S-BM2-...-M0- Pressure drop & A-weighted sound power level in dB(A) Pressure drop & A-weighted sound power level in dB(A) 1000 5000 10000 5000 10000 20000 W: 200, H: 1530 W: 800, H: 2330...
Page 12
12/105 | S-BM2 S-BM2 Grille Types M0, M1 - 2 dampers horizontally assembled into battery S-BM2-...-M0- S-BM2-...-M0- Pressure drop & A-weighted sound power level in dB(A) Pressure drop & A-weighted sound power level in dB(A) 1000 5000 10000 5000 10000 20000 W: 1880, H: 1025 W: 1180, H: 425...
Page 13
13/105 | S-BM2 S-BM2 Grille Types M0, M1 - 4 dampers assembled into battery S-BM2-...-M0- S-BM2-...-M0- Pressure drop & A-weighted sound power level in dB(A) Pressure drop & A-weighted sound power level in dB(A) 5000 10000 20000 10000 20000 50000 W: 1880, H: 2130 W: 1180, H: 1530 W: 1680, H: 1930...
21/105 | S-BM2 Ordering Codes W - Width Dimension 200 mm to 1000 mm and battery dimensions 1180 mm to 2080 mm. In step of 50 mm H - Height Dimensions 425 mm, 625 mm, 825 mm, 1025 mm, 1000 mm and battery dimensions 1530 mm, 1730 mm, 1930 mm, 2130 mm, 2330 mm, 2530 mm.
22/105 | S-BM2 Installation Methods EI 120 (v - i ↔ o) S1000C HOT400/30 S-BM2 ≥ 125 ≥ 125 MAmulti 125 × 325 ... 1000 × 1225 EI 90 (v - i ↔ o) S1000C MAmulti ≥ 125 ≥ 125 EI 90 (v - i ↔...
Page 23
23/105 | S-BM2 EI 120 (v - i ↔ o) S1000C HOT400/30 S-BM2 EN 1366-9 MAmulti EI 120 (h - i ↔ o) EN 1366-8 125 × 325 ... 1000 × 1225 S1000C HOT400/30 MAmulti EI 120 (v - i ↔ o) S1000C HOT400/30 S-BM2...
Page 24
4.Check the damper’s functionality as per the chapter “Smoke Damper Functionality Check” before you install the fire damper. This procedure prevents the installation of a damper that has been damaged during transportation or handling. Information about installation, maintenance and operation is available in the “HandBook_S-BM2” document or more can be found at design.systemair.com.
Page 25
25/105 | S-BM2 Installation 1. WET - in the Wall Using Plaster/Mortar/Concrete Filling 1.The supporting construction opening must be prepared as shown on picture. Opening surfaces must be even and cleaned off. The flexible wall opening must be reinforced as per the standards for plasterboard walls. The opening dimensions are driven by the nominal dimensions of the damper with added clearance.
Page 36
36/105 | S-BM2 Legend for installation 1. WET - in the Wall assembled in battery 1 - Smoke control damper S-BM2 2 - Connected ductwork made of Promatect-L500 boards (min. 500 kg/m3, Promat) 3 - Concrete/masonry/cellular concrete wall or ceiling 5 - Grille 7 - Connected sheet metal ductwork tested according to EN 1366-8 or EN 1366-9 F1 - Plaster/mortar/concrete filling...
Page 37
37/105 | S-BM2 Installation 1. WET - in the Ceiling Using Plaster/Mortar/Concrete Filling 1.The supporting construction opening must be prepared as shown on picture. Opening surfaces must be even and cleaned off. The opening dimensions are driven by the nominal dimensions of the damper with added clearance. The opening will be with the dimensions of W1 and H1.
Page 42
42/105 | S-BM2 Legend for installation 1. WET - in the Ceiling 1 - Smoke control damper S-BM2 2 - Connected ductwork made of Promatect-L500 boards (min. 500 kg/m3, Promat) 3 - Concrete/masonry/cellular concrete wall or ceiling 4 - Flexible (plasterboard) wall 4a - 2 layers of plasterboard fireproof plate type F, EN 520 4b - Vertical CW –...
Page 43
43/105 | S-BM2 Installation 2. DRY Using Mineral Wool and Cover Boards 1.The supporting construction opening must be prepared as shown on picture. Opening surfaces must be even and cleaned off. The flexible wall opening must be reinforced as per the standards for plasterboard walls. The opening dimensions are driven by the nominal dimensions of the damper with added clearance.
Page 49
49/105 | S-BM2 Legend for Installation 2. DRY 1 - Smoke control damper S-BM2 2 - Connected ductwork made of Promatect-L500 boards (min. 500 kg/m3, Promat) 3 - Concrete/masonry/cellular concrete wall or ceiling 4 - Flexible (plasterboard) wall 4a - 2 layers of plasterboard fireproof plate type F, EN 520 4b - Vertical CW –...
Page 50
50/105 | S-BM2 Installation 3. SOFT - in the Wall Using Mineral Wool filing 1.The supporting construction opening must be prepared as shown on picture. Opening surfaces must be even and cleaned off. The flexible wall opening must be reinforced as per the standards for plasterboard walls. The opening dimensions are driven by the nominal dimensions of the damper with added clearance.
Page 59
59/105 | S-BM2 Legend for installation 3. SOFT - in the Wall assembled in battery 1 - Smoke control damper S-BM2 2 - Connected ductwork made of Promatect-L500 boards (min. 500 kg/m3, Promat) 3 - Concrete/masonry/cellular concrete wall or ceiling 4 - Flexible (plasterboard) wall 4a - 2 layers of plasterboard fireproof plate type F, EN 520 4b - Vertical CW –...
Page 60
60/105 | S-BM2 Installation 3. SOFT - in the Ceiling Using Mineral Wool filing 1.The supporting construction opening must be prepared as shown on picture. Opening surfaces must be even and cleaned off. The opening dimensions are driven by the nominal dimensions of the damper with added clearance. The opening will be with the dimensions of W1 and H1.
Page 65
65/105 | S-BM2 Legend for installation 3. SOFT - in the Ceiling 1 - Smoke control damper S-BM2 2 - Connected ductwork made of Promatect-L500 boards (min. 500 kg/m3, Promat) 3 - Concrete/masonry/cellular concrete wall or ceiling 4 - Flexible (plasterboard) wall 4a - 2 layers of plasterboard fireproof plate type F, EN 520 4b - Vertical CW –...
Page 66
66/105 | S-BM2 Installation 3F. Fit Wall build around the damper, filled with mineral wool With this installation the wall is closed off by gypsum board layers around the damper after the insertion of the damper. 1.The opening dimensions are driven by the nominal dimensions of the damper with added clearance. The opening will be with the dimensions of W1 and H1.
Page 69
69/105 | S-BM2 Opening and wall/ceiling preparations...
Page 70
70/105 | S-BM2 Damper minimum distances Legend for installation 3F. Fit 1 - Smoke control damper S-BM2 2 - Connected ductwork made of Promatect-L500 boards (min. 500 kg/m3, Promat) 3 - Concrete/masonry/cellular concrete wall or ceiling 4 - Flexible (plasterboard) wall 4a - 2 layers of plasterboard fireproof plate type F, EN 520 4b - Vertical CW –...
Page 71
71/105 | S-BM2 Installation DBH, DBV - in the Board Duct S-BM2 smoke control damper can be installed on “single” (tested according to EN 1366-9) or “multi” (tested according to EN 1366-8) ductwork. This section does not depict duct hanger rules as those are dependent on the weight of the duct itself and must be statically approved.
Page 73
73/105 | S-BM2 Damper minimum distances Legend for installation DBH, DBV - in the Board Duct 1 - Smoke control damper S-BM2 2 - Connected ductwork made of Promatect-L500 boards (min. 500 kg/m3, Promat) 8 - Cover plate made of Promatect (min. 500 kg/m3, Promat) F4 - Nails or pins per ductwork manufacturer instructions F5 - Fire resistive coating Promat K84 (Promat) A1 - Accessory K1-S-BM2-W×H (size of damper: W = nominal width;...
Page 74
74/105 | S-BM2 Installation DMH, DMV - in the Metal Duct S-BM2 smoke control damper can be installed on “single” (tested according to EN 1366-9) or “multi” (tested according to EN 1366-8) ductwork. This section does not depict duct hanger rules as those are dependent on the weight of the duct itself and must be statically approved.
Page 76
76/105 | S-BM2 Damper minimum distances Legend for installation DMH, DMV - in the Metal Duct 1 - Smoke control damper S-BM2 5 - Grille 7 - Connected sheet metal ductwork tested according to EN 1366-8 or EN 1366-9 8 - Cover plate made of Promatect (min. 500 kg/m3, Promat) A2 - Hanger accessory H1-S-BM2 - can be made on site using 3 mm sheet metal plate.
Page 77
77/105 | S-BM2 Installation D1H, D2H - Horizontally Oriented Damper, On the Duct S-BM2 smoke control damper can be installed on “single” (tested according to EN 1366-9) or “multi” (tested according to EN 1366-8) ductwork. If mounted on a duct classified with lover fire resistivity, the fire resistivity of S-BM2 smoke control damper will be decreased to the duct level.
Page 80
80/105 | S-BM2 Damper minimum distances Legend for installation D1H, D2H - Horizontally Oriented Damper, On the Duct 1 - Smoke control damper S-BM2 2 - Connected ductwork made of Promatect-L500 boards (min. 500 kg/m3, Promat) 5 - Grille 8 - Cover plate made of Promatect (min. 500 kg/m3, Promat) A2 - Hanger accessory H1-S-BM2 - can be made on site using 3 mm sheet metal plate.
Page 81
81/105 | S-BM2 Installation D1V, D2V - Vertically Oriented Damper, On the Duct S-BM2 smoke control damper can be installed on “single” (tested according to EN 1366-9) or “multi” (tested according to EN 1366-8) ductwork. If mounted on a duct classified with lover fire resistivity, the fire resistivity of S-BM2 smoke control damper will be decreased to the duct level.
Page 85
85/105 | S-BM2 Damper minimum distances Legend for installation D1V, D2V - Vertically Oriented Damper, On the Duct 1 - Smoke control damper S-BM2 2 - Connected ductwork made of Promatect-L500 boards (min. 500 kg/m3, Promat) 5 - Grille 8 - Cover plates made of Promatect (min. 500 kg/m3, Promat) A2 - Hanger accessory H1-S-BM2 - can be made on site using 3 mm sheet metal plate.
Page 86
86/105 | S-BM2 Electrical Connections IMPORTANT • Danger of electric shock! • Switch off the power supply before working on any electrical equipment. • Only qualified electricians are allowed to work on the electrical system.
Page 91
91/105 | S-BM2 Legend 1 - Remove the screws and remove the mechanism lid using the 2 straps. 2 - Drill holes in the predefined cut-outs or on the mechanism side of the damper body. 3 - Slide the power and communication wires through the drilled holes. 4 - Fix the wire to avoid any damage from pulling from the outside.
92/105 | S-BM2 Electrical parameters per activation and actuator type B... T (Nm) NV (V) F (Hz) CO (W) CR (W) WS (VA) BEN230 AC 230 50/60 Imax 4 A @ 5 ms B230 BEE230 AC 230 50/60 Imax 4 A @ 5 ms BE230 AC 230 50/60...
Page 94
94/105 | S-BM2 Type of activation B230 • Circuit switch between wires 2 and 3 is not part of the damper delivery. • When power supply is connected to wires 1 and 3, actuator drives to position OPEN. • When power supply is connected to wires 1 and 2, actuator drives to position CLOSED. Notes: •...
Page 95
95/105 | S-BM2 Type of activation B24 • Circuit switch between wires 2 and 3 is not part of the damper delivery. • When power supply is connected to wires 1 and 3, actuator drives to position OPEN. • When power supply is connected to wires 1 and 2, actuator drives to position CLOSED. Notes: •...
Page 96
96/105 | S-BM2 Type of activation B24-W This type of activation is with provided cable connectors for the supply and communication unit (communication unit not part of the mechanism). • Circuit switch between wires 2 and 3 is not part of the damper delivery. •...
Page 97
97/105 | S-BM2 Type of activation B24-SR 24V AC/DC Belimo Actuator, modulated 0..10V • Circuit switch between wires 2 and 3 is not part of the damper delivery. • When power supply is connected to wires 1 and 3, actuator drives to position OPEN. •...
Page 98
98/105 | S-BM2 Type of activation BST • The actuator and the control module are factory wired. • Connect the supply voltage to the connecting cable (approx. 1 m, with ferrules). • The 2-wire cable a/b to the BKSE24-6 is connected to terminals 6 and 7 (screw terminals for 2 x 1.5 mm^2 wire). Terminals 1 and 5 may not be assigned.
Page 99
99/105 | S-BM2 S-BM2 Handling & Manipulation The S-BM2 is made of boards and can thus be considered fragile. Handling and manipulation must be done with care. Smaller dimensions can be manipulated and placed in the installation opening by two persons. Bigger dimensions are supplied with wooden blocks, those serve as support for suitable lifting equipment (forklift, crane). Please follow both textual and graphic instructions: 1.Unpack the damper and place it in vertical position.
102/105 | S-BM2 Legend Y1, Y2, Y3, Y4 - Cutting plane a) - For wall installation - insert the filling as per desired installation. b) - For duct installation – fix the hangers so that the weight of the damper is supported. Operation Manual After installation, it is necessary to adjust the damper into its operating position “closed”. In case, that the damper is used for extraction of pollutants, adjust the damper into its operating position “open”. ...
Page 103
103/105 | S-BM2 Functionality Check Switching the damper to the “open” position: • The blade must come to the fully open position within 60 seconds and must remain locked. • After reaching the end position of the blade, the appropriate signaling circuit must switch on – wires S1 and S2 must be connected.
Page 104
104/105 | S-BM2 Supplement Any deviations from the technical specifications contained herein and the terms should be discussed with the manufacturer. We reserve the right to make any changes to the product without prior notice, provided that these changes do not affect the quality of the product and the required parameters.