Adjustment; Simple Mode Parameter List - Mitsubishi Electric FR-F 700 EC Instruction Manual

Hide thumbs Also See for FR-F 700 EC:
Table of Contents

Advertisement

4 ADJUSTMENT

4.1 Simple mode parameter list

For simple variable-speed operation of the inverter, the initial setting of the parameters may be used as they are. Set the
necessary parameters to meet the load and operational specifications. Parameter setting, change and check can be made from
the operation panel (FR-DU07). For details of parameters, refer to
POINT
Only simple mode parameters are displayed by the initial setting of Pr. 160 User group read selection. Set Pr. 160 User
group read selection as required. (Refer to page 106.)
Pr. 160
9999
Only the simple mode parameters can be displayed.
(Initial Value)
0
Simple mode and extended mode parameters can be displayed.
1
Only the parameters registered in the user group can be displayed.
Parameter
Name
Number
0
Torque boost
Maximum
1
frequency
Minimum
2
frequency
3
Base frequency
Multi-speed setting
4
(high speed)
Multi-speed setting
5
(middle speed)
Multi-speed setting
6
(low speed)
7
Acceleration time
8
Deceleration time
Electronic thermal
9
O/L relay
Energy saving
60
control selection
Operation mode
79
selection
Terminal 2
125
frequency setting
gain frequency
Terminal 4
126
frequency setting
gain frequency
User group read
160
selection
Description
Incre
Initial
Range
ments
Value
6/4/3/2/
0.1%
0 to 30%
1.5/1%
*1
120/
0.01Hz
0 to 120Hz
60Hz
*2
0.01Hz
0Hz
0 to 120Hz
0.01Hz
50Hz
0 to 400Hz
0.01Hz
50Hz
0 to 400Hz
0.01Hz
30Hz
0 to 400Hz
0.01Hz
10Hz
0 to 400Hz
0.1s
5/15s
0 to 3600s
*3
0.1s
10/30s
0 to 3600s
*3
Rated
0.01/
inverter
0 to 500/
0.1A
output
0 to 3600A
*4
current
1
0
0, 4, 9
1
0
0, 1, 2, 3, 4, 6, 7
0.01Hz
50Hz
0 to 400Hz
0.01Hz
50Hz
0 to 400Hz
1
9999
0, 1, 9999

Simple mode parameter list

Instruction Manual (applied).
Applications
Set to increase a starting torque or when the
motor with a load will not rotate, resulting in an
alarm [OL] and a trip [OC1]
*1
Initial values differ according to the inverter
capacity. (00023 / 00038 to 00083 / 00126,00170
/ 00250 to 00770 / 00930, 01160 /01800 or more)
Set when the maximum output frequency need
to be limited.
*2
Initial values differ according to the inverter
capacity. (01160 or less/01800 or more)
Set when the minimum output frequency need
to be limited.
Check the motor rating plate.
Set when changing the preset speed in the
parameter with a terminal.
Acceleration/deceleration time can be set.
*3
Initial values differ according to the inverter
capacity. (00170 or less/00250 or more)
Protect the motor from overheat by the inverter.
Set the rated motor current.
*4
Setting increments and setting range differ
*4
according to the inverter capacity.
(01160 or less/01800 or more)
The inverter output voltage is minimized when
using for fan and pump applications.
Select the start command location and frequency
command location.
Frequency for the maximum value of the
potentiometer (at 5V) can be changed.
Frequency at 20mA input can be changed.
Make extended parameters valid
Refer
to
50
51
52
43
53
4
32
54
56
46
48
49

Advertisement

Table of Contents
loading

Table of Contents