Mitsubishi Electric FR-F 700 EC Instruction Manual page 22

Hide thumbs Also See for FR-F 700 EC:
Table of Contents

Advertisement

Terminal
Terminal
Symbol
Name
10E
Frequency
setting power
supply
10
Frequency
2
setting
(voltage)
Frequency
4
setting
(current)
Frequency
1
setting
auxiliary
Frequency
5
setting
common
(2) Output signals
Terminal
Terminal
Symbol
Name
A1,
Relay output 1
B1,
(alarm output)
C1
A2,
B2,
Relay output 2
C2
Inverter
RUN
running
Up to
SU
frequency
OL
Overload alarm
Instantaneous
IPF
power failure
Frequency
FU
detection
Open collector
SE
output common
Description
When connecting the frequency setting potentiometer at an initial
status, connect it to terminal 10.
Change the input specifications of terminal 2 when connecting it
to terminal 10E. (Refer to Pr. 73 Analog input selection in
Instruction Manual (applied).)
Inputting 0 to 5VDC (or 0 to 10V, 4 to 20mA) provides the
maximum output frequency at 5V (10V, 20mA) and makes input
and output proportional. Use Pr. 73 to switch from among input 0
to 5VDC (initial setting), 0 to 10VDC, and 4 to 20mA.
Inputting 4 to 20mADC (or 0 to 5V, 0 to 10V) provides the
maximum output frequency at 20mA (5V, 10V) makes input and
output proportional. This input signal is valid only when the AU
signal is on (terminal 2 input is invalid). Use Pr. 267 to switch from
among input 4 to 20mA (initial setting), 0 to 5VDC, and 0 to
10VDC.
(Refer to
Instruction Manual (applied).)
Inputting 0 to ±5 VDC or 0 to ±10VDC adds this signal to terminal
2 or 4 frequency setting signal. Use Pr.73 to switch between the
input 0 to ±5VDC and 0 to ±10VDC (initial setting).
Common terminal for frequency setting signal (terminal 2, 1 or 4)
and analog output terminal AM and CA. Do not earth.
Description
1 changeover contact output indicates that the inverter
protective function has activated and the output stopped.
Abnormal: No conduction across B-C (Across A-C Continuity),
Normal: Across B-C Continuity (No conduction across A-C)
1 changeover contact output
Switched low when the inverter output frequency is equal to or higher
than the starting frequency (initial value 0.5Hz). Switched high during
stop or DC injection brake operation.
Switched low when the output frequency
reaches within the range of ±10% (initial
value) of the set frequency. Switched high
during acceleration/deceleration and at a
stop.
*1
Switched low when stall prevention is
activated by the stall prevention
function. Switched high when stall
prevention is cancelled.
*1
Switched low when an instantaneous
power failure and under voltage
protections are activated.
*1
Switched low when the inverter output
frequency is equal to or higher than the
preset detected frequency and high
when less than the preset detected
frequency.
*1
Common terminal for terminals RUN, SU, OL, IPF, FU
*1
Alarm code (4bit)
output
Wiring
Rated
Refer to
Specifications
10VDC
Instruction
Permissible load
Manual
current 10mA
(applied)
5VDC
Permissible load
37, 45
current 10mA
Voltage input:
Input resistance
37, 45
10kΩ ± 1kΩ
Maximum
permissible
voltage 20VDC
Current input:
Input resistance
250Ω ± 5Ω
(while power is on)
39, 47
Maximum
permissible
current 30mA,
10kΩ ± 1kΩ
(while power is off)
Input resistance
10kΩ ± 1kΩ
Instruction
Maximum
Manual
permissible voltage
(applied)
± 20VDC
- -- -- - -- -- - -- -- -- - --
-- -- - -
Rated
Refer to
Specifications
Instruction
Contact capacity:
Manual
230VAC 0.3A
(applied)
(Power
factor=0.4)
Instruction
30VDC 0.3A
Manual
(applied)
Instruction
Manual
(applied)
Instruction
Manual
(applied)
Permissible load
24VDC 0.1A
Instruction
(A voltage drop is
Manual
3.4V maximum
(applied)
when the signal is
on.)
Instruction
Manual
(applied)
Instruction
Manual
(applied)
-- -- -- - -- -- - -- -- -- - -
-- -- -
15
2