netvox R718PE User Manual

netvox R718PE User Manual

Wireless top mounted ultrasonic liquid level sensor
Hide thumbs Also See for R718PE:

Advertisement

Quick Links

Model:R718PE
Wireless Top Mounted Ultrasonic Liquid Level Sensor
Wireless Top Mounted Ultrasonic Liquid Level Sensor
R718PE
User Manual
Copyright©Netvox Technology Co., Ltd.
This document contains proprietary technical information which is the property of NETVOX Technology. It shall be maintained
in strict confidence and shall not be disclosed to other parties, in whole or in part, without written permission of NETVOX
Technology. The specifications are subject to change without prior notice.

Advertisement

Table of Contents
loading

Summary of Contents for netvox R718PE

  • Page 1 This document contains proprietary technical information which is the property of NETVOX Technology. It shall be maintained in strict confidence and shall not be disclosed to other parties, in whole or in part, without written permission of NETVOX Technology. The specifications are subject to change without prior notice.
  • Page 2: Table Of Contents

    Table of Content 1. Introduction ....................................... 2 2. Appearance ......................................2 3. Main Features ....................................3 4. Set up Instruction ....................................4 5. Data Report ....................................... 5 6. Application scenario ..................................10 7. Installation ...................................... 11 8. Information about Battery Passivation ............................13 8.1 To determine whether a battery requires activation........................
  • Page 3: Introduction

    LoRaWAN open protocol and is compatible with the LoRaWAN protocol. R718PE uses ultrasound to detect the distance between the device and the detected object. The medium the device detects is the air, so the detected object can be any liquid or solid that has a flat and horizontal surface, water level.
  • Page 4: Main Features

     Low power consumption and long battery life Note: Battery life is determined by the sensor reporting frequency and other variables, please refer to http://www.netvox.com.tw/electric/electric_calc.html. On this website, users can find battery life time for varied models at different configurations.
  • Page 5: Set Up Instruction

    4. Set up Instruction On/Off Power on Insert batteries. (users may need a flat blade screwdriver to open) Turn on Press and hold the function key for 3 seconds till the green indicator flashes once. Turn off (Restore to factory Press and hold the function key for 5 seconds till green indicator flashes for 20 times.
  • Page 6: Data Report

    1. The device report interval will be programmed based on the default firmware which may vary. 2. The interval between two reports must be the MinTime 3. The data parsing reported by the device is referenced by the Netvox LoRaWAN Application Command document and http://www.netvox.com.cn:8888/page/index Example of ConfigureCmd FPort:0x07...
  • Page 7 (2byte Unit:1mm) (2byte) SetOnDistance OnDistanceThreshold Reserved 0x03 ThresholdRreq (2byte Unit:1mm) (7Bytes,Fixed 0x00) SetOnDistance Status Reserved 0x83 ThresholdRrsp (0x00_success) (8Bytes,Fixed 0x00) R718PE 0x B1 GetOnDistance Reserved 0x04 ThresholdRreq (9Bytes,Fixed 0x00) GetOnDistance OnDistanceThreshold Reserved 0x84 ThresholdRrsp (2byte Unit:1mm) (7Bytes,Fixed 0x00) SetFillMax FillMaxDistance...
  • Page 8 (9Bytes,Fixed 0x00) (1) Set the calibration (GlobalCalibrate configuration): If the distance between the device and the water R718PE detects is 490mm and the actual distance is 500mm, it means the calibration we want to make is +10mm. Channel 1= 00, Multiplier = 000A, Divisor = 0000, DeltValue=0001 Downlink:013600000A000000010000...
  • Page 9 8301000000000000000000(Configuration failure) Note: 1. When Multiplier is not 1, Calibration value = DeltValue*Multiplier. 2. When Divisor is not 1, Calibration value = DeltValue/Divisor. 3. The choices of the Channel would be 00-03 Channel 4. With different sensor type, it is forbidden to use that same Channel number. 5.
  • Page 10 Example#3 based on MinTime = 15 Minutes, MaxTime= 1 Hour, Reportable Change i.e. BatteryVoltageChange= 0.1V. MaxTime Wakes up and collects Users push the button, data REPORTS 3.5V. 3.5V |3.5-3.6|=0.1 Recalculate MaxTime. Wakes up and REPORTS 3.5V collects data 3.5V sleeping sleeping Does not report 1H 10...
  • Page 11: Application Scenario

    6. Application scenario In the use case of detecting the water level in water tanks, the device should be installed on the top of the water tank. After the device is installed and powered, turn on the device and it will detect the distance between the device and the water as well as the percentage of the water level in the water tank.
  • Page 12: Installation

    7. Installation Kindly note the illustration is only for reference. 1. The device can be installed in the middle or anywhere of the top of the container that is flat enough to ensure the ultrasonic detection direction will be vertical to the detected object, so the accuracy can be maintained. 2.
  • Page 13 4. If the top of the water tank can be opened, it is recommended to make a hole of diameter 32mm on the top of the water tank. 5. If the top of the water tank cannot be opened, the hole made on the top of the water tank is recommended to be 45mm diameter. It is recommended to add a gasket (size: 32.4*57.4*3mm) between the hole and the sensor.
  • Page 14: Information About Battery Passivation

    8. Keep the device from electromagnetic disturbances. 8. Information about Battery Passivation Many of Netvox devices are powered by 3.6V ER14505 Li-SOCl2 (lithium-thionyl chloride) batteries that offer many advantages including low self-discharge rate and high energy density. However, primary lithium batteries like Li-SOCl2 batteries will form a passivation layer as a reaction between the lithium anode and thionyl chloride if they are in storage for a long time or if the storage temperature is too high.
  • Page 15: Important Maintenance Instruction

    9. Important Maintenance Instruction Kindly pay attention to the following in order to achieve the best maintenance of the product: • Keep the device dry. Rain, moisture, or any liquid, might contain minerals and thus corrode electronic circuits. If the device gets wet, please dry it completely.