Festo SOPA Operating Instructions Manual

Festo SOPA Operating Instructions Manual

Air gap sensor
Hide thumbs Also See for SOPA:

Advertisement

Quick Links

SOPA
Air gap sensor
Operating instructions
8163013
2021-08d
[8163015]
Translation of the original instructions
© 2021 all rights reserved to Festo SE & Co. KG
1
About this document
1.1
Purpose of the document
This document describes the use of the above-mentioned product. Certain
aspects of use are described in other documents and must be observed è 1.2
Applicable documents.
1.2
Applicable documents
All available documents for the product è www.festo.com/sp.
Document
Description of air gap sensor SOPA
Tab. 1: Applicable documents
2
Safety
2.1
General safety instructions
– Only use the product in its original condition without unauthorised modifica-
tions.
– Only use the product if it is in perfect technical condition.
– Only use media in accordance with the specifications è Technical data.
– Observe labelling on the product.
– Note that changes to the switching status (EDIT mode) become effective imme-
diately.
2.2
Intended Use
The air gap sensor SOPA is intended for distance monitoring in a range of
20 ... 200 µm. The distance measurement is performed using a non-contact pneu-
matic measuring process. This enables it to be used in harsh ambient conditions.
2.3
Training of qualified personnel
Work on the product may only be carried out by qualified personnel who can
evaluate the work and detect dangers. The qualified personnel have skills and
experience in dealing with electrical (open-loop) control technology.
2.4
UL/CSA certification
In combination with the UL inspection mark on the product, the information in this
section must also be observed in order to comply with the certification conditions
of Underwriters Laboratories Inc. (UL) for USA and Canada.
UL/CSA certification information
Product category code
File number
Considered standards
UL mark
Tab. 2: UL/CSA certification information
This device is intended to be used with a Class 2 power source or Class 2 trans-
former in accordance with UL1310 or UL1585.
As an alternative a LV/C (Limited Voltage/Current) power source with one of the
following properties can be used:
Festo SE & Co. KG
Ruiter Straße 82
73734 Esslingen
Deutschland
+49 711 347-0
www.festo.com
Table of contents
Functional description, installation, commis-
sioning, servicing, description of the IO-Link
parameters, technical data
NRNT2/NRNT8
E253738
UL 508
CSA22.2 No. 14
– This device shall be used with a suitable isolating source such that the max-
imum open circuit voltage potential available to the product is not more than
30 V DC and the current is limited to a value not exceeding 8 amperes meas-
ured after 1 minute of operation.
– This device shall be used with a suitable isolating source in conjunction with
a fuse in accordance with UL248. The fuse shall be rated max. 3.3 A and
be installed in the 30 V DC power supply to the device in order to limit the
available current.
3
Additional information
– Contact the regional Festo contact if you have technical problems
è www.festo.com.
– Accessories and spare parts è www.festo.com/catalogue.
– Device description file IODD è www.festo.com/sp.
4
Product overview
4.1
Structure
4.1.1
Product design
18
19
20
17
16
3
15
13
14
13
Fig. 1: Product design
1 Supply port for supply pressure
2 Sensor module (max. 4 modules
permitted in combination with
control module)
3 Plug for electrical connection
4 Display
5 Edit button
6 B pushbutton
7 A pushbutton
8 Label holder
9 Pneumatic port for measuring
nozzle (outlet)
10 Supply port for operating pres-
sure
4.1.2
Display components
1
2
3
4
5
6
Fig. 2: LCD display
1
2
3
4
12
11 Vent screw (width across flats 14)
12 Mounting slides
13 Threaded sleeve (M4)
14 Blanking plug (M7)
15 Control module (optional)
16 Manual LED (green) – ready
indication for manual override
(SOPA-C..-H only)
17 Clean pushbutton (blow-out air)
(SOPA-C..-H only)
18 Status LED (yellow) – clean (blow-
out air)
19 Sense pushbutton (measuring air)
(SOPA-C..-H only)
20 Status LED (yellow) – sense
(measuring air)
Display of binary output OutA
1
2
Display of binary output OutB
3
Display of binary output OutC
4-digit alphanumeric display
4
5
Toolbar for functions
Bar graph
6
5
6
7
8
9
10
11

Advertisement

loading
Need help?

Need help?

Do you have a question about the SOPA and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Festo SOPA

  • Page 1 5 Edit button Intended Use indication for manual override The air gap sensor SOPA is intended for distance monitoring in a range of 6 B pushbutton (SOPA-C..-H only) 20 … 200 µm. The distance measurement is performed using a non-contact pneu-...
  • Page 2 – 7-segment display shows the input value InC. and left and [C] flash. – SHOW mode active. Segments at the bottom left Fig. 4: Binary signals and switching signals SOPA-...-2P/2N-... – 7-segment display shows the minimum or and right and [C] light, [min] or [max] flash.
  • Page 3 The switching output OutC is permanently assigned to monitoring the supply – Tightening torque: 0.5 Nm pressure. The setting is made via the display and buttons or via IO-Link (SOPA-...- 4. Tighten the blanking plugs on the last sensor module by hand.
  • Page 4 B-M7 Tab. 11: Circuit diagrams for control module without manual override Push-in fitting QSM-M7-6-I 6.2.2 PIN allocation and sensor module circuit diagrams 1) Included in the scope of delivery for SOPA-...-W-... Tab. 8: SOPA accessories SOPA-...-2P/-2N Wire colour Allocation Plug...
  • Page 5 SOPA-...-PNLK-VB-... SOPA-...-PNLK-A-... Tab. 15: Circuit diagrams for sensor module Commissioning Commissioning the sensor • Switch on operating voltage. Ä RUN mode is active. To activate the RUN mode at any time, press and hold the Edit button for 3 seconds.
  • Page 6 è 12.1 Technical data, general. [Er21] 0x1815 Short circuit/overload at Rectify short circuit/over- switching output OutA load. (only for SOPA-...-PNLK) [SUP.P] 0x1815 Supply pressure Apply supply pressure Fig. 14: Measured value indicator for SHOW mode switched off è 12.1 Technical data, general.
  • Page 7 General Pneumatic port QS-6 Certification RCM Mark, c UL us - Recognized (OL) 1) Tube length 0.5 … 8 CE marking Declaration of Conformity è www.festo.com/sp Materials Input signal/measuring element Housing Reinforced PA Reinforced Detected variable Distance – Measurement principle pneumatic –...
  • Page 8: Hole Patterns

    10 bit PDV (distance) 12.3 Hole patterns Service data IN 14 bit (supply pressure) Cycle time ³ 3 ms Device ID – SOPA-…-PNLK-VB 0xC0 (192) – SOPA-…-PNLK-A 0xC1 (193) IODD, IO-Link device description è www.festo.com/sp Tab. 21: IO-Link 12.2 Diagrams Response times for different tube lengths Fig.