NOTE: Airflow data shown applies to the electric heat only in either legacy mode or communicating mode operation.
* Within thermostat user menu, CTK04 communicating thermostat will display 20 kW for OFF-OFF-ON dip switch selection and
21 kW for OFF- OFF-OFF dip switch selection.
NR- Not rated
+
For match up with a 2 ton outdoor unit: Heater kit application shall not exceed 10 kW.
Airflow for 5 kW up to 10 kW heater kits shall be set to 850 cfm speed tap of ON-ON-ON.
++
For match up with a 3 ton outdoor unit: Heater kit application shall not exceed 15 kW.
Airflow for 5 kW up to 15 kW heater kits shall be set to 1300 cfm speed tap of ON-OFF-ON.
Airflow for 5 kW up to 20 kW heater kits shall be set to 1500 cfm speed tap of ON-OFF-OFF
** 3 kW heater kit is not applicable for this indoor application.
Models
AVPVC24C14*
X
AVPVC36D14*
AVPVC48D14*
AVPVC60D14*
*Revision level that may or may not be designated.
NOTE: Airflow selection should meet the minimum requirements as mentioned in the air handler installation instructions.
6
Model Name
AVXC200241**
AVXC200361**
AVXC200481**
AVXC200601**
ELECTRIC HEAT AIRFL OW TABLE
11
AVPVC24C14*
ON
730
OFF
780
ON
850
OFF
950
ON
1025
OFF
N R
N R
ON
N R
OFF
N R
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
TXV-Kit
TXV-V24
TXV-V36
TXV-V48
TXV-V60
AVPVC36D 14A+
850**
1250
1300
1500
1550
1720
NR
1800
NR
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
AVPVC48D 14*++
NR
1250
1300
1500
1550
1720
NR
1815
1850
X
X
X
X
X
X
AVPVC60D 14++
N R
1250
1300
1500
1550
1780
N R
1850
1850
X
X
X
X
X
X
X
X
X
X
X

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Avxc200241Avxc200361Avxc200481Avxc200601

Table of Contents