SERVICING
PVE oils maintain a consistent viscosity over a large temperature range which aids in the oil return to the compressor; however,
there will be some installations which require oil return traps. These installations should be avoided whenever possible, as
adding oil traps to the refrigerant lines also increases the opportunity for debris and moisture to be introduced into the system.
Avoid long running traps in horizontal suction line.
NOTE: If line set is installed on the exterior of an outside wall, similar installation practices are to be used.
Hanger
Wall
Stud
Metal
Sleeve
Figure 1-1.
Installation of Refrigeration Piping From Vertical to Horizontal
IMPORTANT - Refrigerant lines must not touch wall.
Outside Wall
Wood Block
Between Studs
Armaflex
®
Wrapped
Suction Line
Outside Wall
Liquid
Line
Caulk
PVC Pipe
Fiberglass Insulation
I
MPORTANT:
Refrigerant lines must NOT
come into contact with structure.
Figure 1-2. Installation of Refrigerant Piping (Vertical)
New construction shown
Liquid Line
Strapped to
Suction Line
Liquid Line
Suction Line
Wrapped in Armaflex
®
Suction Line
Liquid Line
Wire Tie
Inside Wall
Strap
Sleeve
Wood
Wire Tie
Block
Strap
Sleeve
47