SERVICING
SECTION 4. OUTDOOR UNIT IS BELOW THE INDOOR UNIT
Condenser BELOW Evaporator
1. The maximum elevation (vertical) difference between the outdoor unit and the indoor unit is 90 feet.
2. Suction line must be installed in a manner to prevent liquid migration to the outdoor unit from the
indoor unit.
The condenser unit is shipped with a predetermined factory charge level as shown in the following chart. For longer line sets greater
than 15 feet, add 0.6 ounces of refrigernat per foot.
45°
Ell
Short Radius
Street Ell
Figure 3-1. Oil Trap
equivalent length of 250 ft*.
The maximum line set actual length is 200 ft.
*Accounts for pressure losses of any elbows, bends, etc.
NOTICE
T
R
=
OTAL
EFRIGERANT
F
C
+ (0.6
./
ACTORY
HARGE
OZ
A
L
S
).
OF
CTUAL
INE
ET
Long Radius Street Ell
45°
Street Ell
Maximum line set
. * A
F
FT
DDITIONAL
EET
49