SERVICING
NOTE: Upon start up in communicating mode the circuit board may display an "Ec"
error. This is an indication that the dip switches on the control board need to be
configured in accordance with the Electric Heating Airflow Table. Configuring the
dip switches and resetting power to the unit will clear the error code.
Within the thermostat user menu, CTK04 communicating thermostat will display
20 kW for OFF-OFF-ON dip switch selection and 21 kW for OFF-OFF-OFF dip switch
selection.
T
ROUBLESHOOTING
E
D
LECTROSTATIC
ISCHARGE
NOTE: Discharge body's static electricity before touching unit.
An electrstaic can adversly affect electrical components.
Use the following precautions during air handler installation
and servicing to protect the integrated control module from
damage. By putting the air handler, the control, and ther per-
son at the same electrostatic potentential, these steps will help
avoid exposing the integrated control module to electrostatic
discharge. This procedure is applicable to both installed and
uninstalled (ungrounded) blowers.
1. Disconnect all power to the blower. Do not touch the
integrated control module or any wire connected to the
control prior to discharging your body's electrostatic
charge to ground.
2. Firmly touch a clean, unpainted, metal surface of the
air handler blower near the control. Any tools held in a
person's hand during grounding will be discharged.
3. Service integrated control module or connecting wiring
following the discharge process in step 2. Use caution
not to recharge your body with static electricity; (i.e., do
not move or shuffle your feet, do not touch ungrounded
objects, etc.). If you come in contact with an ungrounded
object, repeat step 2 before touching control or wires.
4. Discharge your body to ground before removing a new
control from its container. Follow steps 1 through 3 if
installing the control on a blower. Return any old or
new controls to their containers before touching any
ungrounded object.
(ESD) P
RECATIONS
AVPVC24C14*
AVPVC36C14*
AVPVC48C14*
AVPVC60C14*
D
C
IAGNOSTIC
HART
HIGH VOLTAGE!
T
O AVOID PERSONAL INJURY OR DEATH DUE TO
,
ELECTRICAL SHOCK
DISCONNECT ELECTRICAL POWER
BEFORE PERFORMING ANY SERVICE OR MAINTENANCE
Refer to the Troubleshooting Chart at the end of this manual for
assistance in determining the source of unit operational prob-
lems. The 7 segment LED display will provide any active fault
codes. An arrow printed next to the display indicates proper
orientation (arrow points to top of display). See following image.
F
R
AULT
ECALL
The integrated control module is equipped with a momentary
push-button switch that can be used to display the last six faults
on the 7 segment LED display. The control must be in Standby
Mode (no thermostat inputs) to use the feature. Depress the push-
button for approximately two seconds. The LED display will then
display the six most recent faults beginning with the most recent
fault and decrementing to the least recent fault. The faults may
be cleared by depressing the button for greater than five seconds.
NOTE: Consecutively repeated faults are displayed a maximum of
three times. Example: A clogged return air filter causes the air
handler's motor to repeatedly enter a limiting condition. The
control will only store this fault the first three consecutive times
the fault occurs.
Airflow Table
Airflow
Model
CFM
Level
690
High
495
Low
1165
High
795
Low
1430
High
870
Low
1640
High
1070
Low
WARNING
.
7 Segment
Diagnostic
Display
53