Amana AVXC20 Series Service Instructions Manual page 48

Inverter condensing unit
Table of Contents

Advertisement

SERVICING
If hanging line set from a joist or rafter,
use metal strapping
or heavy nylon wire tires
that are securely anchored.
SECTION 3. OUTDOOR UNIT IS ABOVE THE INDOOR UNIT
1.
Suction line must be sloped continuously towards the indoor unit.
2.
The maximum elevation (vertical) difference between the outdoor unit and indoor unit is 200'.
3.
The maximum line set equivalent length is 250', which includes pressure losses of any elbow, bends, etc. The maximum line
set actual length is 200'.
4.
Inverted suction loop is not required at either unit.
5.
An accumulator is not required for air conditioners (accumulators are factory installed ).
48
8'
Floor Joist or
Roof Rafter
Metal Sleeve
Strapping placed
around the suction line only
T ape or Wire Tie
Figure 1-3. Installation of Refrigerant Piping (Horizontal)
Condenser ABOVE Evaporator
*Accounts for pressure losses of any elbows, bends, etc.
Wire Tie
(around suction line only)
T ape or Wire Tie
8'
After the suction line has been strapped to the joist or rafter at 8' intervals,
strap the liquid line to the suction line.
Maximum line set
equivalent length of 250 ft.*
The maximum line set
actual length is 200 ft.
Floor Joist or Roof Rafter
Maximum vertical
separation of 200 ft.

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Avxc200241Avxc200361Avxc200481Avxc200601

Table of Contents