the emergency stop during operation will lead to immediate unloading of the motor guard
while there is still power on Unisab III. Therefore, it is always possible to read the compressor
state.
Whenever the emergency stop is activated during operation, the alarm text Compr. motor er-
ror will appear in the display. Before the compressor can be restarted, deactivate the alarm
F4
by means of the
/RESET key and release the emergency stop.
Please note: If Unisab III is set at Remote or Auto, the compressor will restart automatically.
Power supply:
Consumption:
Ambient temperature:
Humidity:
Tightness:
Engineering manual - Unisab III 1.10
001930 en 2014.09
Technical data
Nominal VAC
Tolerance
85-250
32 VA
0-55°C (during operation)
10-90% relative humidity (not condensing)
IP 54
3/319
Hz
47-63
Need help?