8. Technical Specifications

MultiPlus-II 48V 3kVA 120V
PowerControl & PowerAssist
Transfer switch
Maximum AC input current
DC Input voltage range
Output when in inverter mode
Cont. output power at 25°C (3)
Cont. output power at 25°C
Cont. output power at 40°C
Cont. output power at 65°C
Maximum apparent feed-in power
Peak power
Maximum efficiency
Zero load power
Zero load power in AES mode
Zero load power in Search mode
Maximum output current
AC Input
Charge voltage 'absorption'
Charge voltage 'float'
Storage mode
Maximum battery charge current (4)
Battery temperature sensor
Auxiliary output
External AC current sensor (optional)
Programmable relay (5)
Protection (2)
VE.Bus communication port
General purpose com. port
Remote on-off
Operating temperature range
Humidity (non-condensing)
Material & Colour
Protection category
Battery-connection
Page 25
MultiPlus-II 48V 3kVA 120V
INVERTER
Output voltage: 120 VAC ± 2%
CHARGER
Split phase: 190-280 VAC 45 – 65 Hz
Single phase: 95-140 VAC 45 – 65 Hz
GENERAL
For parallel and three phase operation, remote monitoring
-40 to +65°C (fan assisted cooling)
ENCLOSURE
Yes
50 A
50 A
38 - 66 V
Frequency: 60 Hz ± 0,1% (1)
3000 VA
2400 W
2200 W
1700 W
2500 VA
5500 W
93%
13 W
9 W
3 W
85 A peak, 70Arms for 1sec.
57.6 V
55.2 V
52.8 V
35 A
Yes
Yes (50 A)
100 A
Yes
a – g
and system integration
Yes, 2x
Yes
max 95%
Steel, blue RAL 5012
IP22
M8 bolts