Victron energy MultiPlus-II Manual page 26

48v 3kva 120v
Hide thumbs Also See for MultiPlus-II:
Table of Contents

Advertisement

All of the conditions below must be met!:
1. The device is in error! (No AC output)
2. Inverter LED flashes (in opposition to any flashing of the Bulk, Absorption or Float LED)
3. At least one of the LEDs Bulk, Absorption and Float is on or flashing
Bulk LED off
Float LED
off
flashing
on
Bulk LED flashes
Float LED
off
flashing
on
Bulk LED on
Float LED
off
flashing
on
Bulk LED Absorption
LED Float LED
Page 23
MultiPlus-II 48V 3kVA 120V
Absorption LED
off
flashing
on
0
3
6
1
4
7
2
5
8
Absorption LED
off
flashing
on
9
12
15
10
13
16
11
14
17
Absorption LED
off
flashing
on
18
21
24
19
22
25
20
23
26
Code
Meaning:
1
Device is switched off because
one of the other phases in the
system has switched off.
3
Not all, or more than, the
expected devices were found in
the system.
4
No other device whatsoever
detected
Cause/solution:
Check the failing phase.
The system is not properly configured.
Reconfigure the system.
Communication cable error. Check the
cables and switch all equipment off, and then
on again.
Check the communication cables.
Error Indications