Installation instructions for WSC sleeve

WARNING
Falling Object Hazard
Not following Installation Instructions
for mounting your air conditioner can
result in property damage, injury, or
death.
Mounting hardware provided
ITEM NO.
DESCRIPTION
1
SCREW, #12A x 2"

Wall preparation

STEP 1
The wall opening required for a WSC SLEEVE is 17 ¼"
high by 27 ¼" wide.
STEP 2
LINTELS must be used in opening of brick veneer and
masonry walls to support the material above the WSC
SLEEVE. The following considerations should also be given:
Figure 7
From Top Of Unit To Ceiling.
10
QTY.
Minimum Of 24" Required
Inside Wall
Minimum Of 1" Spacing
Required On All Sides
Of The Unit.
1" Minimum
3 ½" For Subbase
920-007-14
7
A. Adjustable SUBBASE (SB) or other unit support must be provided
for panel wall type construction and for walls less than 8" thick.
B. A minimum distance of 1" must be allowed on all sides of the unit
to adjacent wall and fl oor. Where the subbase is required, the
minimum distance from the fl oor to the sleeve must be 3 ½". To
minimize chances of short cycling of the compressor, the minimum
clearance between the ceiling and the top of the unit should be
24". (See Figure 7).
Lintels
WSC Sleeve
Drain
Extension
9
" Minimum
1 6
Beyond Outside
Wall
Outside Wall