Special precautions providing high noise immunity

Inductors require
snubber networks
Power outlet for
PGs
Cubicle
illumination
Suppression of
fluorescent lamps
in cubicles
HB160E - TP - RE_606-1BC40 - Rev. 08/13
Inductors controlled by your programmable controller (e.g. contactors and
relays) do not normally require additional snubber networks or suppressors
as the respective modules have been provided with the required
components.
Snubber networks must only be connected to inductors when output
circuits can be disabled by means of additional contacts (e.g. relay
contacts). In this case the integrated suppressors on the module are also
disabled.
You can connect diodes to suppress back-emc, varistors or RC-networks
to the inductors.
Connections of
DC-activated inductors
using a diode
using a Z-diode using a varistor
+
+
-
-
Every cubicle must be provided with a power outlet for the PU. These
outlets must be wired to the distribution system, which is also used to
connect the neutral conductor for the cubicle.
The cubicle illumination should consist of incandescent lights, e.g.
LINESTRA-lamps. Avoid using fluorescent lamps as these lamps can
cause interference.
If you can not avoid using fluorescent lamps you should implement the
steps outlined in the following figure.
1
2
Chapter 3 Installation Guidelines
Connections of
AC-activated inductors
[1]
Fluorescent lamp
3
[2]
Screen above the lamp
4
[3]
Screened cable
[4]
Switch with metallic cover
5
[5]
Line filter or screened power
cable
using RC-network
3-11