Manual VIPA HMI

EMC-equitable cabling

Line routing
Line routing inside
and outside of
cubicles
HB160E - TP - RE_606-1BC40 - Rev. 08/13
Content of this section is the line routing of bus, signal and supply lines.
Object of the line routing is to suppress the "slurring" at parallel lines.
For an EMC-equitable routing of the lines it is convenient to divide the
cables in different groups and install each group itself:
Group A
• screened bus and data lines
• screened analog lines
• unshielded lines for direct voltage ≤ 60V
• unshielded lines for alternating voltage ≤ 25V
• Coaxial cables for monitors
Group B
• unshielded lines for direct voltage >60V and ≤400V
• unshielded lines for alternating voltage >25V and ≤400V
Group C
• unshielded lines for direct and alternating voltage >400V
Group D
• Lines for H1 respectively TCP/IP
Chapter 3 Installation Guidelines
3-7