Manual VIPA HMI
Settings
Parameter of
StartupMngr.dat
Parameter
VISUALISATION
LOCATION
FILE
FONT
PASSWORD
BACKROUND
AUTOLAUNCHDELAY
HB160E - TP - RE_606-1BC40 - Rev. 08/13
The settings of the VIPA Startup Manager are stored in the file
StartupMngr.dat. This file may be found on the Touch Panel at My Device
> Flashdisk.
Within this file the settings of the VIPA Startup Manager may be changed
by parameters.
Note!
This file is hidden as default. To make this file visible within Windows
every option of My Device > View > Options is to be deactivated.
Depending on the installed visualization software the following parameters
are used:
Meaning
Indicates which visualization software is used.
Indicates the file location of the visualization software.
Path and file name of the last started project.
Indicates the storage location of additional fonts to be registered.
Here a password may be entered. Before returning to Windows
you are asked for this password.
Path and file name of the background picture.
Here a delay time in seconds may be set. If this time is passed the
preset project is started automatically.
Please consider this during setting parameters:
Parameter and value is always be connected by "=". Blanks are not
allowed. For the parameter names capitals are to be used.
The whole path is to be used when entering a file location e.g.
BACKGROUND=\flashdisk\background.jpg