Banner SureCross DX80 Series Manual

Banner SureCross DX80 Series Manual

Configurable node with analog inputs and analog outputs
Hide thumbs Also See for SureCross DX80 Series:

Advertisement

Quick Links

SureCross DX80 Node
Configurable Node with analog inputs and analog outputs
IP67 Base
2.4 GHz
IP20 Base
900 MHz
For additional information, updated documentation, and accessories, refer to Banner Engineering's website,
ing.com/surecross.
Models
DX80N9X6S0P0V4V4
DX80N2X6S0P0V4V4
DX80N9X6S0P0V4V4C
DX80N2X6S0P0V4V4C
Internal antenna models are also available, but are not UL Listed. For more information, contact your local Banner Engineering Corp.
representative.
WARNING: Not To Be Used for Personnel Protection
Never use this device as a sensing device for personnel protection. Doing so could lead to serious
injury or death. This device does not include the self-checking redundant circuitry necessary to allow its
use in personnel safety applications. A sensor failure or malfunction can cause either an energized or de-
energized sensor output condition.
SureCross User Configuration Tool
P/N 136326 Rev. E
The SureCross® wireless system is a radio frequency network with integrated I/O that can
operate in most environments and eliminate the need for wiring runs. Wireless networks are
formed around a Gateway, which acts as the wireless network master device, and one or
more Nodes.
• Wireless industrial I/O device with four 0 to 10V analog inputs and four 0 to 10V analog
outputs
• 10 to 30V dc power input
• DIP switches for user configuration
• Frequency Hopping Spread Spectrum (FHSS) technology and Time Division Multiple Ac-
cess (TDMA) control architecture ensure reliable data delivery within the unlicensed Indus-
trial, Scientific, and Medical (ISM) band
• Transceivers provide bidirectional communication between the Gateway and Node, includ-
ing fully acknowledged data transmission
• Lost RF links are detected and relevant outputs set to user-defined conditions
• The DX80...C models are certified for use in Class I, Division 2, Group A, B, C, D; Zone 2
(Category 3G) Hazardous Locations when properly installed in accordance with the Na-
tional Electrical Code, the Canadian Electrical Code, or applicable local codes/regulations
(see Specifications)
Frequency
Environmental Rating
900 MHz ISM Band
IP67, NEMA 6
2.4 GHz ISM Band
900 MHz ISM Band
IP20, NEMA 1
Class I, Division 2, Group A, B, C, D
Hazardous Locations (see Specifica-
2.4 GHz ISM Band
tions)
The User Configuration Tool (UCT) offers an easy way to link I/O points in your wire-
less network, view I/O register values graphically, and set system communication pa-
rameters when a host system is not part of the wireless network.
The UCT requires a special USB to RS-485 (model number BWA-UCT-900 for 1 Watt
radios, BWA-HW-006 can be used for all other radios) converter cable to pass infor-
mation between your computer and the Gateway. Download the most recent revi-
sions of the UCT software from Banner Engineering's website:
gineering.com/wireless.
5/22/2013
www.bannerengineer-
I/O
Inputs: Four 0 to 10V analog
Outputs: Four 0 to 10V analog
http://www.banneren-
0 136326
5

Advertisement

Table of Contents
loading

Summary of Contents for Banner SureCross DX80 Series

  • Page 1 DX80N2X6S0P0V4V4C 2.4 GHz ISM Band tions) Internal antenna models are also available, but are not UL Listed. For more information, contact your local Banner Engineering Corp. representative. WARNING: Not To Be Used for Personnel Protection Never use this device as a sensing device for personnel protection. Doing so could lead to serious injury or death.
  • Page 2: Setting Up Your Wireless Network

    For additional information, including installation and setup, weatherproofing, device menu maps, troubleshooting, and a list of accesso- ries, refer to one of the following product manuals. • SureCross Quick Start Guide: Banner part number 128185 • SureCross Wireless I/O Network Manual: 132607 •...
  • Page 3 SureCross DX80 Node Switches Device Settings Link loss output: zero OFF* OFF* Link loss output: one Link loss output: hold last state Link loss output: user configuration 0–20 mA scale (Not used on 0–10V I/O models.) OFF* 4–20 mA scale (Not used on 0–10V I/O models.) * Default configuration Address Mode The SureCross wireless devices may use one of two types of addressing modes: rotary dial addressing or extended addressing.
  • Page 4: Terminal Blocks

    SureCross DX80 Node Terminal Label Gateway, DX85 10 to 30V dc Powered Nodes Battery Powered Nodes 10 to 30V dc 10 to 30V dc Tx/+ RS485 / D1 / B / + dc common (GND) dc common (GND) dc common (GND) Rx/- RS485 / D0 / A / - 3.6 to 5.5V dc...
  • Page 5: Led Behavior For The Nodes

    SureCross DX80 Node Analog Output Wiring 10-30V dc sensor dc common LED Behavior for the Nodes After powering up and binding the Gateway and its Nodes, verify all devices are communicating properly. A Node will not sample its inputs until it is communicating with its Gateway. When testing communication between the Gateway and Node, all radios and antennas should be at least two meters apart or the communications may fail.
  • Page 6 SureCross DX80 Node Radio and General Range Power 900 MHz: Up to 4.8 kilometers (3 miles) Requirements: +10 to 30V dc (Outside the USA: +12 to 24V dc, ±10%). (See UL section below for any applica- 2.4 GHz: Up to 3.2 kilometers (2 miles) ble UL specifications) Transmit Power Consumption: Less than 1.4 W (60 mA) at 24V dc...
  • Page 7: Banner Engineering Corp Limited Warranty

    Banner Engineering Corp Limited Warranty Banner Engineering Corp. warrants its products to be free from defects in material and workmanship for one year following the date of shipment. Banner Engineering Corp. will repair or replace, free of charge, any product of its manufacture which, at the time it is returned to the factory, is found to have been defective during the warranty period.
  • Page 8 ER ARISING IN CONTRACT OR WARRANTY, STATUTE, TORT, STRICT LIABILITY, NEGLIGENCE, OR OTHERWISE. Banner Engineering Corp. reserves the right to change, modify or improve the design of the product without assuming any obligations or liabilities relating to any product previously manufactured by Banner Engineering Corp.

This manual is also suitable for:

Surecross dx80n9x6s0p0v4v4Surecross dx80n2x6s0p0v4v4Surecross dx80n9x6s0p0v4v4cSurecross dx80n2x6s0p0v4v4c