Wiring
Base module with cage clamp terminals:
}
Please note:
The minimum cable cross section for field connection terminals on the base modules is
}
0.14 mm
The maximum cable cross section for field connection terminals is:
}
Operating Manual PSSu E PD1(-T)
21453-EN-04
Insert the screwdriver [4] into the square hole [1].
Insert the stripped cable into the round fixing hole [2], as far as it will go [5].
Pull out the screwdriver [6].
Check that the cable is firmly seated.
11
(AWG26).
2
Digital inputs: 1.5 mm
2
Digital outputs: 2.0 mm
Inputs/outputs on the counter modules: 1.5 mm
Analogue inputs/outputs: 1.5 mm
Communication cables: 1.5 mm
Test pulse outputs: 1.5 mm
Power supply: 2.5 mm
2
Functional earth: 2.5 mm
21
(AWG16)
(AWG14)
2
(AWG16)
2
(AWG16)
2
(AWG16)
2
(AWG12)
(AWG12)
2
[1]
[2]
[3]
[4]
[5]
[6]
(AWG16)
2
18