9.4.5 Communication Menu
This section describes each item on the communication menu. Use this menu to configure the communication
options. The password to access this menu is 3.
Parameter Name
Port 1 Baud
Choose the baud rate for the primary serial port
Parameter Name
Port 1 Addr
Set the address for the primary serial port
Port 2 Baud
Choose the baud rate for the primary serial port
Parameter Name
Watchdog
Enable or disable the watchdog on the primary serial port
Parameter Name
WD Reset
Set the amount of time to wait for a message
before triggering the watchdog error.
This function is available only for Modbus
RTU Protocol
Description
Option
9600
19.2K
38.4K
115.2K
DEFAULT: 38.4K
Description
Option
9600
19.2K
38.4K
115.2K
DEFAULT: 38.4K
Option
Off
On
DEFAULT: Off
Description
Value
0
1
2
3
2
Value
0
1
2
3
2
Description
Value
0
1
0
Default
37
User's manual
Default
2
Default
Range
1
0 to 255
2
Default
0
Range
Unit
5
0 to 255
Sec
Modbus
Par.
Address
Type
Read
30
Write
Modbus
Par.
Address
Type
Read
31
Write
Read
45
Write
Modbus
Par.
Address
Type
Read
142
Write
Modbus
Par.
Address
Type
Read
143
Write