Power Supply - Siemens SIMATIC NET SCALANCE X-000 Series Operating Instructions Manual

Industrial ethernet switches
Table of Contents

Advertisement

Note
Wire end ferrules
Use crimp shapes with smooth surfaces, such as provided by square and trapeze shaped
crimp cross sections.
Crimp shapes with wave-shaped profile are unsuitable.
6.3

Power supply

The power supply is connected using a 2-terminal plug-in block. The power supply is connected
over a high resistance with the enclosure to allow an ungrounded set up. The power supply is
non-floating.
Note
The device can be disconnected from the power supply with the terminal block.
The following figure shows the position of the power supply of the SCALANCE X-000 and the
assignment of the terminal block.
Contact
M
L+
Incorrect power supply
The power supply unit to supply the device must comply with NEC Class 2 (voltage range 18
- 32 V, current requirement 350 mA).
Do not operate the device with an AC voltage.
Never operate the device with DC voltages higher than 32 VDC.
SCALANCE X-000
Operating Instructions, 12/2018, C79000-G8976-C344-03
Assignment
Ground
L+ 24 VDC
WARNING
Connecting up
6.3 Power supply
29