Connecting up

6.5 IE FC RJ-45 Plug 180

6.4

Grounding

Installation on a DIN rail
The device is grounded over the DIN rail.
S7 standard rail
The device is grounded over its rear panel and the neck of the screw.
Wall mounting
The device is grounded by the securing screw in the unpainted hole.
Note that the device must be grounded over a securing screw with as low a low resistance as
possible.
If the device is mounted on a non-conductive base, a grounding cable must be fitted. The
grounding cable is not supplied with the device. Connect the paint-free surface of the device
to the nearest grounding point using the grounding cable.
6.5
IE FC RJ-45 Plug 180
The rugged node connectors are designed for industry with PROFINET-compliant connectors
and provide additional strain and bending relief with a locking mechanism on the casing.
Fitting the IE FC RJ45 Plug 180 to the IE FC Standard Cable
You will find the notes on installation in the instructions that ship with the IE FC RJ45 Plug 180.