Service Tools - Daikin VRV III-S RXYMQ6PV4A Service Manual

For high outdoor temperature use, r-410a
Table of Contents

Advertisement

SiME34-608
1.3

Service Tools

R-410A is used under higher working pressure, compared to previous refrigerants
(R-22,R-407C). Furthermore, the refrigerating machine oil has been changed from Suniso oil to
Ether oil, and if oil mixing is occurred, sludge results in the refrigerants and causes other
problems. Therefore, gauge manifolds and charge hoses that are used with a previous
refrigerant (R-22,R-407C) can not be used for products that use new refrigerants.
Be sure to use dedicated tools and devices.
Gauge manifold
Charge hose
Charging cylinder
Gas detector
Vacuum pump
(pump with reverse flow
preventive function)
Weighting instrument
Charge mouthpiece
Flaring tool (Clutch type)
Torque wrench
Pipe cutter
Pipe expander
Pipe bender
Pipe assembling oil
Refrigerant recovery
device
Refrigerant piping
* O: Soft (Annealed)
Precautions for New Refrigerant (R-410A)
Tool compatibility
Tool
R-410A
Check your recovery device.
As for the charge mouthpiece and packing, 1/2UNF20 is necessary for mouthpiece size of
charge hose.
Copper tube material and thickness
Pipe size
Material
φ6.4
φ9.5
φ12.7
φ15.9
φ19.1
φ22.2
1/2H
φ25.4
1/2H
φ28.6
1/2H
φ31.8
1/2H
φ38.1
1/2H
φ44.5
1/2H
H: Hard (Drawn)
Compatibility
HFC
HCFC
R-407C
R-22
See the chart below.
R-407C
Thickness
t (mm)
O
0.8
O
0.8
O
0.8
O
1.0
O
1.0
1.0
1.0
1.0
1.2
1.4
1.6
Precautions for New Refrigerant (R-410A)
Reasons for change
2Do not use the same tools for R-22
and R-410A.
2Thread specification differs for
R-410A and R-407C.
2Weighting instrument used for HFCs.
2The same tool can be used for HFCs.
2To use existing pump for HFCs,
vacuum pump adaptor must be
installed.
2Seal material is different between
-
22 and HFCs.
R
2Thread specification is different
between R-410A and others.
2For R-410A, flare gauge is necessary.
2Torque-up for 1/2 and 5/8
2Due to refrigerating machine oil
change. (No Suniso oil can be used.)
2Only φ19.1 is changed to 1/2H material
while the previous material is "O".
R-410A
Material
O
O
O
O
1/2H
1/2H
1/2H
1/2H
1/2H
1/2H
1/2H
Thickness
t (mm)
0.8
0.8
0.8
1.0
1.0
1.0
1.0
1.0
1.1
1.4
1.6
239